Neutral Earthing Resistor Formulas

Neutral earthing resistor formulas: the resistance for a ground fault current limit, the power in the resistor during a fault and the energy for a rated time.

The formulas

To findFormula
Phase voltageVp = VL / √3
Resistance for a current limitR = Vp / Ig
Power during a faultP = Ig² × R = Vp × Ig
Energy for the rated timeE = P × t

VL is the line voltage of the system, Ig the ground fault current that the resistor lets through and t the time rating of the resistor. The formulas take a solid fault from one phase to earth and ignore the impedance of the source and the cable, so the real current is a little lower. The resistor is rated for a short time, such as 10 s, because the protection clears the fault, and it needs a longer rating if the fault can stay. The current limit comes from the protection design, the cable screens and the damage allowed, and the values here are examples.

Worked example: an 11 kV system with a limit of 400 A

  1. Vp = 11,000 / √3 = 6,351 V
  2. R = 6,351 / 400 = 15.88 Ω
  3. P = 400² × 15.88 = 2.54 MW
  4. For a rating of 10 s, E = 2.54 × 10 = 25.4 MJ

Resistance and power for an 11 kV system by current limit

Current limitResistancePower in the fault
50 A127 Ω0.3175 MW
100 A63.51 Ω0.6351 MW
200 A31.75 Ω1.27 MW
400 A15.88 Ω2.54 MW
1000 A6.351 Ω6.351 MW

Frequently asked questions

Why limit the ground fault current?

A lower fault current means less damage to the machine and the cables, lower step and touch voltages and less stress on the system, while still giving a current that the protection can sense.

What is the trade-off?

A lower current is harder to detect, and it calls for a sensitive earth fault relay. A higher current gives easier protection but more damage.

What other limits does the resistor have?

A continuous rating for a neutral current in service, a voltage rating at the neutral and a temperature rise limit. The maker states them.

What is the difference from a solid earth?

A solidly earthed system lets the full fault current flow and has no neutral resistor. The resistor trades fault current for lower damage.

Related

Earthing FormulasShort-Circuit FormulasStep and Touch Voltage FormulasEarthing and grounding calculatorsThree-Phase Power FormulasPower Factor and the Power TriangleAC Circuit Formulas: Reactance and ImpedanceVoltage Drop Formulas for CablesTransformer Formulas: Current and Fault LevelInduction Motor FormulasLighting Formulas: Lux, Lumens and CandelaBattery Formulas: Capacity and RuntimeSolar PV Formulas: Array Size and StringsCapacitor Formulas: Energy and RC Time ConstantCable Size Formulas: Current and Short-CircuitEnergy and Cost Formulas: kWh and PaybackGenerator Formulas: kVA, Current and FuelUPS Formulas: kVA, DC Current and BatteryHarmonics Formulas: THD and True Power FactorUnbalance Formulas: Voltage and Neutral CurrentResistor Formulas: Series, Parallel, DividerMotor Starting Formulas: DOL, Star-DeltaCircuit Breaker Formulas: Rating and TripCooling Formulas: Airflow and Heat LoadHeating Formulas: Energy and Heater PowerPer-Unit Formulas: Base Values and ImpedanceLED Formulas: Resistor Value and PowerConduit Fill Formulas: Percent Fill and SizeLightning Protection Formulas: Rolling SphereTransformer Efficiency and Regulation FormulasPump Formulas: Hydraulic, Shaft and Motor PowerFan Formulas: Air Power and Affinity LawsInductor Formulas: Energy and L/R Time ConstantRMS, Peak and Average Value FormulasResonance Formulas: Frequency, Q, BandwidthMotor Efficiency Formulas: Input and SavingsDemand, Load and Diversity Factor FormulasCable Tray Fill Formulas: Area and Cable CountConductor Resistance Formulas and TemperatureTransmission Line Formulas: Drop and LossesStar-Delta Conversion Formulas for Resistors4-20 mA Loop Formulas: Scaling and ResistorCable Loss Formulas: Power and Annual CostOp-Amp Formulas: Inverting and Non-Inverting555 Timer Formulas: Frequency and Duty CycleThévenin and Norton FormulasWheatstone Bridge Formulas: Balance and OutputConductor Force Formulas: Short-Circuit ForcesCT Burden Formulas: Lead Resistance and VAGear and Belt Drive Formulas: Speed and TorqueSkin Effect Formulas: Skin DepthRC Filter Formulas: Cutoff Frequency and GainRectifier Ripple Formulas: Capacitor FilterBuck and Boost Converter Formulas: Duty CycleHeat Sink Formulas: Junction TemperatureBattery Pack Formulas: Series and ParallelMotor Acceleration Time FormulasZener Regulator Formulas: Series ResistorBJT Bias Formulas: Voltage Divider BiasPt100 RTD Formulas: Resistance and TemperatureNTC Thermistor Formulas: Beta EquationFusing Current Formulas: Wire Fuse EstimateFlywheel Formulas: Stored EnergyLinear Regulator Formulas: Power and EfficiencyMOSFET Loss Formulas: Conduction and SwitchingRelay Coil Formulas: Current and ResistorTransformer Inrush Current FormulasBattery Charge Time FormulasWind Turbine Power Formulas: Betz LimitDetuning Reactor Formulas: Capacitor BanksTransformer Tap Changer FormulasCable Pulling Tension FormulasInsulation Resistance Formulas: PI and DARPower Transfer and Power Angle FormulasSolar Panel Temperature Derating FormulasVoltage Change and Flicker FormulasSoft Starter and VFD Sizing FormulasEarth Fault Loop and RCD FormulasBattery Internal Resistance FormulasBusbar Size and Short-Circuit FormulasADC Resolution and Sampling FormulasCapacitor Switching Inrush FormulasCable Charging Current FormulasSolar DC to AC Ratio FormulasMeasurement Uncertainty FormulasParallel Transformer Load Sharing FormulasPeukert Law and Battery Runtime FormulasCapacitor Discharge Time FormulasHydraulic Power and Cylinder Force FormulasThermocouple Voltage FormulasTransformer Vector Group FormulasPower Supply Hold-Up Time FormulasHoist and Lift Power FormulasCompressor Power FormulasRectifier Bridge Sizing FormulasPCB Trace Width and Current FormulasHeat Pump COP FormulasSound Level and dB Addition FormulasDuty Cycle and RMS Load FormulasSupercapacitor Energy FormulasContactor Sizing FormulasInverter-Fed Motor Cable FormulasPneumatic Cylinder Force and Air UseBusbar Temperature Rise FormulasMotor Temperature Rise FormulasBattery Storage Round-Trip EfficiencyThermal Time Constant FormulasSolar Charge Controller Sizing FormulasPoint Illuminance FormulasGenerator Droop and Load Sharing FormulasTwo-Wattmeter Method FormulasVFD Braking Resistor FormulasLoad Bank Test FormulasTransformer Cooling Class Rating FormulasEnergy Meter Multiplier FormulasOvercurrent Relay Curve FormulasSingle-Tuned Harmonic Filter FormulasCable Sheath Circulating Current FormulasDifferential Protection Slope FormulasEarth Electrode Spacing FormulasSolar Array Row Spacing FormulasDC Lighting Voltage Drop FormulasTransformer Loss of Life FormulasMotor Start Voltage Dip in the Cable FormulasCable I²t Withstand Check FormulasMotor Locked-Rotor Code Letter FormulasSynchronous Speed and Pole FormulasBattery C-Rate and Cycle Life FormulasEV Charging Time FormulasConveyor Belt Power FormulasParallel Plate Capacitor FormulasSolenoid and Coil Inductance FormulasPower Factor Correction Payback FormulasTransformer Through-Fault Current FormulasTransformer EMF Equation FormulasDelta-Star Resistor Conversion FormulasCurrent Shunt Resistor FormulasSolar Energy Yield and Degradation FormulasElectrolysis and Faraday’s Law FormulasAGL Series Circuit Load and CCR Sizing FormulasAGL Maximum Fittings on a CCR FormulasAGL Isolating Transformer FormulasAGL CCR Input Power and Energy FormulasAGL Brightness Step FormulasAGL Lamp Life FormulasComplex Number Formulas: Polar and RectangularPhasor Addition Formulas: Sum and DifferencePercentage Error Formulas for MeasurementsTrigonometry Formulas for Electrical EngineersMean and Standard Deviation FormulasQuadratic, Logarithm and Power FormulasPercentage, Ratio and Rounding FormulasProbability, Combinations and Binomial FormulasConversion Centre