Contactor Sizing Formulas

Motor contactor formulas: the full-load current of the motor, the AC-3 contactor rating with a margin and the starting current the contacts must make.

The formulas

To findFormula
Motor full-load currentI = P × 1000 / (√3 × V × η × pf)
Contactor AC-3 rating neededIe ≥ I / k
Starting current to makeIst = m × I

P is the shaft power in kW, V the line voltage, η the efficiency and pf the power factor of the motor at full load, k a derating factor for the ambient temperature, the altitude and the starts per hour (1 if the maker gives none), and m the ratio of the starting current to the full-load current, often 6 to 8 for a direct-on-line start. The AC-3 rating is the rated operational current of a contactor that starts squirrel-cage motors and breaks them while they run. Plugging and inching (AC-4) need a much larger contactor or a lower rating from the maker's table. Take the motor current from the nameplate when it is known. The list of sizes, 0.9, 7, the efficiency and the power factor here are examples, and each maker has its own series.

Worked example: a 30 kW motor on 415 V

Efficiency 0.92, power factor 0.86, derating 0.9.

  1. I = 30,000 / (√3 × 415 × 0.92 × 0.86) = 52.75 A
  2. Ie ≥ 52.75 / 0.9 = 58.61 A, so the next size in the example list is 65 A
  3. Ist = 7 × 52.75 = 369.3 A

Full-load current on 415 V (efficiency 0.92, power factor 0.86)

Motor powerFull-load current
7.5 kW13.19 A
15 kW26.38 A
30 kW52.75 A
55 kW96.71 A

Frequently asked questions

What does AC-3 mean?

It is the utilisation category of the standard for starting squirrel-cage motors and switching them off while they run. The rating of a contactor depends on the category.

Why add a margin?

High ambient temperature, many starts and the contact wear lower the usable rating, so the contactor is chosen above the motor current.

Does the contactor protect the motor?

No. A contactor switches the load. The short-circuit protection and the overload relay are separate devices, and the contactor must be co-ordinated with them.

What about star-delta and soft starters?

The contactors in a star-delta starter carry a part of the line current. Use the maker's table, or see the motor starting and soft starter articles for the currents.

Related

Induction Motor FormulasMotor Starting FormulasCircuit Breaker FormulasMotor engineering calculatorsThree-Phase Power FormulasPower Factor and the Power TriangleAC Circuit Formulas: Reactance and ImpedanceVoltage Drop Formulas for CablesTransformer Formulas: Current and Fault LevelLighting Formulas: Lux, Lumens and CandelaBattery Formulas: Capacity and RuntimeSolar PV Formulas: Array Size and StringsCapacitor Formulas: Energy and RC Time ConstantEarthing Formulas: Earth Rod and Fault LoopCable Size Formulas: Current and Short-CircuitEnergy and Cost Formulas: kWh and PaybackGenerator Formulas: kVA, Current and FuelUPS Formulas: kVA, DC Current and BatteryHarmonics Formulas: THD and True Power FactorShort-Circuit Formulas: Fault Level by MVAUnbalance Formulas: Voltage and Neutral CurrentResistor Formulas: Series, Parallel, DividerCooling Formulas: Airflow and Heat LoadHeating Formulas: Energy and Heater PowerPer-Unit Formulas: Base Values and ImpedanceLED Formulas: Resistor Value and PowerConduit Fill Formulas: Percent Fill and SizeLightning Protection Formulas: Rolling SphereTransformer Efficiency and Regulation FormulasPump Formulas: Hydraulic, Shaft and Motor PowerFan Formulas: Air Power and Affinity LawsInductor Formulas: Energy and L/R Time ConstantRMS, Peak and Average Value FormulasResonance Formulas: Frequency, Q, BandwidthMotor Efficiency Formulas: Input and SavingsDemand, Load and Diversity Factor FormulasCable Tray Fill Formulas: Area and Cable CountConductor Resistance Formulas and TemperatureTransmission Line Formulas: Drop and LossesStar-Delta Conversion Formulas for Resistors4-20 mA Loop Formulas: Scaling and ResistorCable Loss Formulas: Power and Annual CostOp-Amp Formulas: Inverting and Non-Inverting555 Timer Formulas: Frequency and Duty CycleThévenin and Norton FormulasWheatstone Bridge Formulas: Balance and OutputConductor Force Formulas: Short-Circuit ForcesCT Burden Formulas: Lead Resistance and VAGear and Belt Drive Formulas: Speed and TorqueSkin Effect Formulas: Skin DepthRC Filter Formulas: Cutoff Frequency and GainRectifier Ripple Formulas: Capacitor FilterBuck and Boost Converter Formulas: Duty CycleHeat Sink Formulas: Junction TemperatureBattery Pack Formulas: Series and ParallelMotor Acceleration Time FormulasZener Regulator Formulas: Series ResistorBJT Bias Formulas: Voltage Divider BiasPt100 RTD Formulas: Resistance and TemperatureNTC Thermistor Formulas: Beta EquationFusing Current Formulas: Wire Fuse EstimateFlywheel Formulas: Stored EnergyLinear Regulator Formulas: Power and EfficiencyMOSFET Loss Formulas: Conduction and SwitchingRelay Coil Formulas: Current and ResistorTransformer Inrush Current FormulasBattery Charge Time FormulasWind Turbine Power Formulas: Betz LimitDetuning Reactor Formulas: Capacitor BanksTransformer Tap Changer FormulasCable Pulling Tension FormulasInsulation Resistance Formulas: PI and DARPower Transfer and Power Angle FormulasSolar Panel Temperature Derating FormulasVoltage Change and Flicker FormulasSoft Starter and VFD Sizing FormulasEarth Fault Loop and RCD FormulasBattery Internal Resistance FormulasBusbar Size and Short-Circuit FormulasADC Resolution and Sampling FormulasCapacitor Switching Inrush FormulasCable Charging Current FormulasSolar DC to AC Ratio FormulasMeasurement Uncertainty FormulasParallel Transformer Load Sharing FormulasPeukert Law and Battery Runtime FormulasCapacitor Discharge Time FormulasHydraulic Power and Cylinder Force FormulasThermocouple Voltage FormulasTransformer Vector Group FormulasPower Supply Hold-Up Time FormulasHoist and Lift Power FormulasCompressor Power FormulasRectifier Bridge Sizing FormulasPCB Trace Width and Current FormulasHeat Pump COP FormulasSound Level and dB Addition FormulasDuty Cycle and RMS Load FormulasSupercapacitor Energy FormulasStep and Touch Voltage FormulasInverter-Fed Motor Cable FormulasPneumatic Cylinder Force and Air UseBusbar Temperature Rise FormulasMotor Temperature Rise FormulasBattery Storage Round-Trip EfficiencyThermal Time Constant FormulasSolar Charge Controller Sizing FormulasPoint Illuminance FormulasGenerator Droop and Load Sharing FormulasTwo-Wattmeter Method FormulasVFD Braking Resistor FormulasLoad Bank Test FormulasTransformer Cooling Class Rating FormulasEnergy Meter Multiplier FormulasOvercurrent Relay Curve FormulasSingle-Tuned Harmonic Filter FormulasCable Sheath Circulating Current FormulasDifferential Protection Slope FormulasEarth Electrode Spacing FormulasSolar Array Row Spacing FormulasDC Lighting Voltage Drop FormulasTransformer Loss of Life FormulasMotor Start Voltage Dip in the Cable FormulasNeutral Earthing Resistor FormulasCable I²t Withstand Check FormulasMotor Locked-Rotor Code Letter FormulasSynchronous Speed and Pole FormulasBattery C-Rate and Cycle Life FormulasEV Charging Time FormulasConveyor Belt Power FormulasParallel Plate Capacitor FormulasSolenoid and Coil Inductance FormulasPower Factor Correction Payback FormulasTransformer Through-Fault Current FormulasTransformer EMF Equation FormulasDelta-Star Resistor Conversion FormulasCurrent Shunt Resistor FormulasSolar Energy Yield and Degradation FormulasElectrolysis and Faraday’s Law FormulasAGL Series Circuit Load and CCR Sizing FormulasAGL Maximum Fittings on a CCR FormulasAGL Isolating Transformer FormulasAGL CCR Input Power and Energy FormulasAGL Brightness Step FormulasAGL Lamp Life FormulasComplex Number Formulas: Polar and RectangularPhasor Addition Formulas: Sum and DifferencePercentage Error Formulas for MeasurementsTrigonometry Formulas for Electrical EngineersMean and Standard Deviation FormulasQuadratic, Logarithm and Power FormulasPercentage, Ratio and Rounding FormulasProbability, Combinations and Binomial FormulasConversion Centre