Elecmetric

Battery Bank Sizing Calculator

Size a battery bank in Ah from load power, backup time, bank voltage, depth of discharge and inverter efficiency, with the formula and a worked example.

Load power 500 W, backup time 4 h, battery bank voltage 48 V, usable depth of discharge 0.8 gives
Required capacity: 57.9 Ah · Energy from battery: 2.222 kWh

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

Use this to find the battery capacity needed to carry a constant load for a set backup time. It allows for the usable depth of discharge and the inverter efficiency, and gives the energy drawn from the battery as well as the capacity in amp-hours.

Limits of this calculator

No ageing, temperature or Peukert allowance is included. Add an ageing margin (typically 20 to 25%) and a temperature factor before selecting the battery, and use the capacity quoted at the discharge rate of your backup time.

Cross-check: 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Indicative

Indicative. Estimation only; further engineering checks are required. Basis: Sizing estimate from simple derating factors.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionIEEE 485; IEC 62485-2, IEEE 485-2020 (active); IEC 62485-2:2010
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteStationary lead-acid battery sizing and stationary battery safety are relevant. IEEE 485 applies to lead-acid float-service applications; the calculator is a simplified energy estimate and does not implement duty-cycle sizing.
Cross-check test cases6 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusIndicative

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

Ah = P × t / (V × DoD × η)

Worked example

InputValue
Load power500 W
Backup time4 h
Battery bank voltage48 V
Usable depth of discharge0.8
Inverter efficiency0.9
  1. Energy = P × t / η = 500 × 4 / 0.9 = 2,222.2 Wh
  2. Ah = 2,222.2 / (48 × 0.8) = 57.87 Ah

Assumptions

Add an ageing margin (typically 20 to 25%) and a temperature factor before selecting the battery.

Inputs and results

InputUnitAllowed or shownNote
Load powerWgreater than 0 W
Backup timehgreater than 0 h
Battery bank voltageVgreater than 0 V
Usable depth of discharge(number)greater than 0, up to 1
Inverter efficiency(number)greater than 0, up to 1
ResultUnitAllowed or shownNote
Required capacityAhShown to 1 decimal place
Energy from batterykWhShown to 3 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

Typical values

Backup time (h)Required capacity (Ah)Energy from battery (kWh)
114.50.556
228.91.111
457.92.222
8115.74.444
12173.66.667

Other inputs are the same as in the worked example above.

Standards and further reading

Check results against your utility's connection requirements and the equipment data sheets. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter load power, backup time, battery bank voltage, usable depth of discharge and inverter efficiency. Change the unit of a value with its selector and the result stays the same.

Why is the Ah more than the energy divided by the voltage?

Only part of the battery can be used, set by the depth of discharge, and the inverter loses some energy. The formula divides by both, so the bank must be larger than the plain energy figure.

Should I add a margin to the result?

Yes. The result is the capacity needed when new, at the rated temperature. Batteries lose capacity with age and in the cold, so add an ageing margin and a temperature factor.

How is this different from battery runtime?

This works from the backup time you need to the capacity required. The UPS runtime calculator goes the other way, from a given battery to the time it can carry the load.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Power Systems calculatorsAll engineering calculatorsBattery Bank Sizing in Elecmetric

Tell us how to improve this page