Motor Full-Load Current Calculator

Estimate the full-load current of a three-phase or single-phase motor from kW, voltage, power factor and efficiency, with the formula and worked example.

Shaft power 250 kW, line voltage (L-L) 415 V, power factor 0.88, efficiency 0.95 gives
Full-load current: 416 A · Electrical input power: 263.2 kW

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

Use this when you know the motor rating in kW but not the current, for example while choosing a starter, a cable or a breaker before the nameplate is available. Efficiency and power factor are inputs because the line current depends on both, not on the shaft power alone.

Limits of this calculator

This is a planning estimate. When the motor nameplate gives a full-load current, use the nameplate value. Starting current is not included; the motor starting calculator covers it.

Cross-check: 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Engineering reference

Engineering reference. Formula and method documented and tested against separately coded reference calculations. Not yet Verified: the evidence listed on this page is still needed.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionIEC 60034-1, 2026 Ed 15
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteRotating-machine rating and performance context. The equation estimates input current from output power, efficiency, power factor and voltage; nameplate data takes precedence.
Cross-check test cases6 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusEngineering reference

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

I = P / (η × √3 × V × pf)

Worked example

InputValue
Shaft power250 kW
Line voltage (L-L)415 V
Power factor0.88
Efficiency0.95
PhaseThree-phase
  1. Input power = 250 kW / 0.95 = 263.16 kW
  2. I = 263,158 / (1.7321 × 415 × 0.88) = 416.03 A

Assumptions

Nameplate values should be preferred. Use this for planning when only kW is known.

Inputs and results

InputUnitAllowed or shownNote
Shaft powerkWgreater than 0 kW
Line voltage (L-L)Vgreater than 0 V
Power factor(number)greater than 0, up to 1Rough starting point only. Resistive heating and incandescent loads are 1.0; a fully loaded induction motor is typically 0.8 to 0.88 and falls sharply when lightly loaded; discharge lighting depends on its ballast or driver. For real work use the nameplate or a measured value.
Efficiency(number)greater than 0, up to 1
Phase(choice)Three-phase; Single-phase
ResultUnitAllowed or shownNote
Full-load currentAShown to 1 decimal place
Electrical input powerkWShown to 1 decimal place

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

Typical values

Shaft power (kW)Full-load current (A)Electrical input power (kW)
5.59.25.8
1118.311.6
2236.623.2
5591.557.9
110183.1115.8
250416263.2
400665.6421.1

Other inputs are the same as in the worked example above.

Standards and further reading

Where the motor nameplate or data sheet gives a value, use it in place of a calculated one. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter shaft power, line voltage (L-L), power factor and efficiency. Change the unit of a value with its selector and the result stays the same.

Why is the current higher than the rated kW divided by the voltage?

The kW rating is shaft power. The motor draws more electrical power than that because of its losses (efficiency), and for the same power a lower power factor means more current. The formula divides by efficiency, power factor, the voltage and √3 for three-phase.

Should I use the nameplate current instead?

Yes, when you have it. The nameplate figure is measured for that motor. Use the calculated value only for planning when the nameplate or data sheet is not available yet.

Does this give the starting current?

No. Starting current is several times the full-load current and depends on the starting method. Use the motor starting current calculator with the full-load current from this page.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Motor Engineering calculatorsAll engineering calculatorsMotor Full-Load Current in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.