Elecmetric

Cable Derating and Ampacity Calculator

Derate a cable for ambient temperature and grouping to get its usable current capacity, and the tabulated ampacity you must start from for a given breaker.

Design current 160.4 A, protective device rating 200 A, tabulated ampacity (data sheet, reference conditions) 300 A, calculation basis General / IEC-style (70 / 90 °C, 30 °C table ambient) gives
Temperature factor: 0.913 · Derated current capacity: 219.1 A · Tabulated ampacity required: 273.9 A

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

Use this to find the current a cable can actually carry once the ambient temperature and grouping are accounted for, or the tabulated ampacity a cable must have to be protected by a given device. It also checks the design current against the device rating and the derated capacity.

Limits of this calculator

Tabulated ampacities are not built in, because they depend on the installation method and come from licensed standards. Enter the value from your cable data sheet or the standard. The calculation bases apply the factors listed in the assumptions below; they are not complete regional table lookups, so check the result against the standard you work to.

Cross-check: 30 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Indicative

Indicative. Estimation only; further engineering checks are required. Basis: Temperature factor is a heat-balance approximation, not the tabulated standard factor.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionIEC 60364-5-52, 2009 + A1:2024, consolidated Ed 3.1
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteCable current-carrying capacity and correction factors are relevant. The in-app square-root temperature factor is a simplified heat-balance approximation, not a tabulated IEC derating factor; group and other factors are user inputs.
Cross-check test cases30 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusIndicative

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

kt = √((θmax − Ta) / (θmax − Tref)) Iz = Itab × kt × kg × ko Itab,req = In / (kt × kg × ko)

Worked example

InputValue
Design current160.4 A
Protective device rating200 A
Tabulated ampacity (data sheet, reference conditions)300 A
Calculation basisGeneral / IEC-style (70 / 90 °C, 30 °C table ambient)
InsulationXLPE / EPR (90 °C conductor)
Ambient temperature (°C)40
User-defined conductor limit (°C)90
User-defined factor on design current1
Reference ambient of the tabulated value (°C)30
Grouping factor0.8
Other correction factor1
  1. θmax = 90 °C
  2. kt = √((90 − 40) / (90 − 30)) = 0.9129
  3. Combined factor = 0.9129 × 0.8 × 1 = 0.7303
  4. Iz = 300 × 0.7303 = 219.09 A
  5. Required tabulated ampacity = 200 / 0.7303 = 273.86 A

Assumptions

The temperature multiplier is an engineering approximation, not a substitute for the ambient-temperature correction factor in the applicable wiring standard or cable-manufacturer tables. For final cable selection, use the prescribed factor for the actual cable type, installation method, ambient conditions and grouping. Tabulated ampacity values are not built in because they depend on installation method and may be protected data; read them from your data sheet or licensed standard.

Inputs and results

InputUnitAllowed or shownNote
Design currentAgreater than 0 A
Protective device ratingAgreater than 0 A
Tabulated ampacity (data sheet, reference conditions)Agreater than 0 AValue from the cable manufacturer or your applicable standard for the installation method
Calculation basis(choice)General / IEC-style (70 / 90 °C, 30 °C table ambient); IS India (70 / 90 °C, 40 °C table ambient); BS 7671 UK (70 / 90 °C, 30 °C table ambient) - provisional, not checked against the 2026 amendment; AS/NZS 3008 ampacity basis (75 / 90 °C, 40 °C table ambient) - provisional, not checked against the 2025 edition; NEC-style (75 / 90 °C, 125% on continuous load); User-defined (set below in Engineering mode)
Insulation(choice)PVC (70 °C; 75 °C under AS/NZS and NEC-style); XLPE / EPR (90 °C conductor)
Ambient temperature (°C)(number)-50 or more, up to 80
User-defined conductor limit (°C)(number)50 or more, up to 250Used only with the user-defined basis
User-defined factor on design current(number)1 or more, up to 2Used only with the user-defined basis; 1.25 for continuous loads under NEC-style rules
Reference ambient of the tabulated value (°C)(number)-50 or more, up to 8030 °C for cables in air in IEC-based tables; check your data sheet
Grouping factor(number)0.1 or more, up to 1From the grouping table for your installation method
Other correction factor(number)0.1 or more, up to 1.5Soil resistivity, depth, harmonics or similar
ResultUnitAllowed or shownNote
Temperature factor (approx.)(number)Shown to 3 decimal places
Derated current capacityAShown to 1 decimal place
Tabulated ampacity requiredAShown to 1 decimal place
Minimum device rating for this basisAShown to 1 decimal place

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

Typical values

Ambient temperature (°C)Temperature factorDerated current capacity (A)Tabulated ampacity required (A)
301240250
350.957229.8261.1
400.913219.1273.9
450.866207.8288.7
500.816196306.2
550.764183.3327.3

Other inputs are the same as in the worked example above.

Standards and further reading

Ampacity and grouping factors come from your cable data sheet or your licensed copy of the standard; see STANDARDS.md for the method constants Elecmetric does use. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter design current, protective device rating, tabulated ampacity (data sheet, reference conditions), calculation basis, insulation, ambient temperature (°C) and grouping factor. Change the unit of a value with its selector and the result stays the same.

Where do I get the tabulated ampacity?

From the cable manufacturer data sheet or the installation table in the standard you work to, for your installation method and conductor. Elecmetric applies the correction factors to that figure; it does not look it up.

How is the temperature factor worked out?

It comes from the heat balance of the conductor, the square root of the margin between the conductor limit and the ambient, over the margin between the conductor limit and the reference ambient of the table. The formula above shows it.

Is cable ampacity a separate calculation from derating?

No. The derated current capacity is the ampacity for your conditions, so this one page covers both questions.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 30 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Cable Engineering calculatorsAll engineering calculatorsCable Derating and Ampacity in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.