Generator Sizing Calculator

Size a generator in kVA from running load, power factor and design margin, rounded to a standard rating, with the rated line current at that size.

Running load 400 kW, power factor 0.8, design margin (%) 25, line voltage (L-L) 415 V gives
Required rating: 625 kVA · Next standard size: 625 kVA · Rated current at that size: 870 A

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

Use this for a first estimate of the generator rating needed to carry a known running load. It converts kW to kVA with the power factor, adds your design margin, rounds up to a standard size and gives the rated current of that size for the breaker and cable.

Limits of this calculator

This covers the running load only. Motor starting, non-linear loads, and altitude or temperature derating need a separate check and can raise the size. Only the required rating is cross-checked against separately coded values; the standard-size table and rated current are not yet.

Cross-check: 67 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Indicative

Indicative. Estimation only; further engineering checks are required. Basis: Sizing estimate; starting and transient loads need a full study.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionISO 8528-1, 2018 Ed 3 (published edition; Ed 4 DIS was under development at review date)
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteDefines generating-set application, ratings and performance. The calculator only estimates kVA from kW, power factor and a user margin; load steps, ambient derating and engine/alternator ratings are not assessed.
Cross-check test cases67 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusIndicative

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

S = P / pf × (1 + margin) I = S / (√3 × V)

Worked example

InputValue
Running load400 kW
Power factor0.8
Design margin (%)25
Line voltage (L-L)415 V
  1. S = 400 / 0.8 × 1.25 = 625 kVA
  2. Next standard size = 625 kVA
  3. I = 625 kVA / (√3 × 415) = 869.5 A

Assumptions

Motor starting, non-linear loads and altitude or temperature derating need a separate check and can raise the size.

Inputs and results

InputUnitAllowed or shownNote
Running loadkWgreater than 0 kW
Power factor(number)greater than 0, up to 1Rough starting point only. Resistive heating and incandescent loads are 1.0; a fully loaded induction motor is typically 0.8 to 0.88 and falls sharply when lightly loaded; discharge lighting depends on its ballast or driver. For real work use the nameplate or a measured value.
Design margin (%)(number)0 or more, up to 100Growth and loading headroom
Line voltage (L-L)Vgreater than 0 V
ResultUnitAllowed or shownNote
Required ratingkVAShown to 1 decimal place
Next standard sizekVAShown to 1 decimal place
Rated current at that sizeAShown to 0 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

Typical values

Running load (kW)Required rating (kVA)Next standard size (kVA)Rated current at that size (A)
5078.1100139
100156.3200278
200312.5320445
400625625870
8001,2501,2501,739

Other inputs are the same as in the worked example above.

Standards and further reading

Check results against your utility's connection requirements and the equipment data sheets. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter running load, power factor, design margin (%) and line voltage (L-L). Change the unit of a value with its selector and the result stays the same.

Why does the generator size depend on power factor?

Generators are rated in kVA, while loads are usually known in kW. The same kW at a lower power factor needs more kVA, so the calculator divides the running load by the power factor.

Does this allow for motor starting?

No. Large motors can pull the voltage down at start and may need a larger set. Check them with the motor starting current and voltage dip calculators.

What design margin should I add?

It is a design choice that covers growth and uncertainty in the load figure. Use the figure your specification or client sets; the calculator adds it as a percentage.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 67 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.