Maximum Demand Calculator

Coincident maximum demand from connected load, demand factor and diversity factor. With the formula, a worked example and typical values.

Connected load 500 kW, demand factor 0.7, diversity factor 1.2, power factor 0.9 gives
Maximum demand: 291.7 kW · Maximum demand: 324.1 kVA

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

This page calculates maximum demand and maximum demand from connected load, demand factor, diversity factor and power factor. Change any value or its unit and the result updates. The steps below show the working for the default values, so you can check each line against your own method.

Limits of this calculator

Use factors from your project specification or standard; the defaults are only examples.

Cross-check: 15 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Indicative

Indicative. Estimation only; further engineering checks are required. Basis: Demand-factor estimate.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionNot applicable: Demand and diversity factors depend on the adopted wiring code, occupancy and utility rules. The calculator accepts user-defined factors and does not implement a specific standard method.
Standard review stateNot applicable
Scope-screening notenot recorded
Cross-check test cases15 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusIndicative

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; exact formula reference; formula source (textbook or standard); next review date.

Formula

MD = connected × demand factor / diversity factor S = MD / pf

Worked example

InputValue
Connected load500 kW
Demand factor0.7
Diversity factor1.2
Power factor0.9
  1. MD = 500 × 0.7 / 1.2 = 291.67 kW
  2. S = 291.67 / 0.9 = 324.07 kVA

Assumptions

Use factors from your project specification or standard; the defaults are only examples.

Inputs and results

InputUnitAllowed or shownNote
Connected loadkWgreater than 0 kW
Demand factor(number)greater than 0, up to 1
Diversity factor(number)1 or more, up to 5
Power factor(number)greater than 0, up to 1Rough starting point only. Resistive heating and incandescent loads are 1.0; a fully loaded induction motor is typically 0.8 to 0.88 and falls sharply when lightly loaded; discharge lighting depends on its ballast or driver. For real work use the nameplate or a measured value.
ResultUnitAllowed or shownNote
Maximum demandkWShown to 1 decimal place
Maximum demandkVAShown to 1 decimal place

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

How the result changes with connected load

Connected load (kW)Maximum demand (kW)Maximum demand (kVA)
5029.232.4
12572.981
250145.8162
500291.7324.1
1,000583.3648.1
2,0001,166.71,296.3
5,0002,916.73,240.7

Other inputs are the same as in the worked example above.

Standards and further reading

Real, apparent and reactive power follow the usual textbook definitions. Tariff and billing rules come from your utility, not from a standard. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter connected load, demand factor, diversity factor and power factor. Change the unit of a value with its selector and the result stays the same.

What does this calculator assume?

Demand factor = max demand ÷ connected load for each group. Diversity factor ≥ 1 reflects groups peaking at different times.

Which calculators should I use next?

Common next steps are Transformer kVA Selection and Generator kVA Selection. The related links at the bottom of this page open them.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 15 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Power and Energy calculatorsAll engineering calculatorsMaximum Demand in Elecmetric