Amps to kW Calculator
Convert Amps to kW with the formula, a worked example and a table of typical values. Working shown step by step.
Try your own numbers
Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.
Open in the calculator with these values
Formula
Worked example
| Input | Value |
|---|---|
| Line current | 100 A |
| Voltage | 400 V |
| Power factor | 0.9 |
| Current type | Three-phase AC |
| Voltage type (three-phase only) | Line-to-line (L-L) |
| Efficiency | 0.92 |
- P = √3 × 400 × 100 × 0.9 = 62.3538 kW
- Output = η × P = 0.92 × 62.3538 = 57.3655 kW
Typical values
| Line current (A) | Real power (kW) | Output power (P × η) (kW) |
|---|---|---|
| 5 | 3.118 | 2.868 |
| 10 | 6.235 | 5.737 |
| 20 | 12.471 | 11.473 |
| 50 | 31.177 | 28.683 |
| 100 | 62.354 | 57.366 |
| 200 | 124.708 | 114.731 |
| 500 | 311.769 | 286.828 |
Other inputs are the same as in the worked example above.
Assumptions
- Balanced load
- V is line-to-line RMS for three-phase unless line-to-neutral is chosen
- DC takes the power factor as 1
- Efficiency 1 means output power equals input power
Real power is electrical input power. Output (shaft) power is P × η and equals P when efficiency is 1.
Frequently asked questions
How do I convert Amps to kW?
P = √3 × V × I × pf (three-phase L-N: 3 × V × I × pf; single-phase: V × I × pf; DC: V × I); Output = η × P. Worked example: Line current 100 A, voltage 400 V, power factor 0.9, current type Three-phase AC gives Real power: 62.354 kW · Output power: 57.366 kW.
What do I need to enter?
Enter line current, voltage, power factor, current type, voltage type (three-phase only) and efficiency. Change the unit of a value with its selector and the result stays the same.
Does single-phase or three-phase change the answer?
Yes. Pick the circuit type that matches the supply. Three-phase uses √3 with the line-to-line voltage, single-phase uses the voltage as it is, and DC, where it is offered, takes the power factor as 1. The formula above shows each case.
Which power factor should I use?
Read it from the equipment nameplate or data sheet. Typical values are only a guide: about 1.0 for a resistive load and about 0.85 for a fully loaded induction motor. Do not use typical values for accurate work.
How accurate are the results?
Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. Check design values against the standard and the equipment data you work to.
Related
Next steps in a design: Amps to kVAThree-Phase Power
Opposite direction: kW to Amps
Also see: HP to Amps Amps to HP Amps to kVA kVA to Amps
Formula guides: Three-Phase Power FormulasPower Factor and the Power TriangleAC Circuit Formulas: Reactance and Impedance
All 78 conversionsAmps to kW in Elecmetric