Elecmetric

Power Factor Correction Calculator

Capacitor kVAR needed to raise power factor to a target. With the formula, a worked example and typical values.

Real power 100 kW, present power factor 0.8, target power factor 0.95 gives
42.13 kVAR

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

This page calculates capacitor rating from real power, present power factor and target power factor. Change any value or its unit and the result updates. The steps below show the working for the default values, so you can check each line against your own method.

Limits of this calculator

Round up to the next standard capacitor step and check for resonance on harmonic-rich systems.

Cross-check: 10 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Engineering reference

Engineering reference. Formula and method documented and tested against separately coded reference calculations. Not yet Verified: the evidence listed on this page is still needed.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionNot applicable: Textbook power and energy identity (single-phase, three-phase, power factor, per-unit); no governing standard
Standard review stateNot applicable
Scope-screening notenot recorded
Cross-check test cases10 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusEngineering reference

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; exact formula reference; formula source (textbook or standard); next review date.

Formula

Qc = P × (tan φ1 − tan φ2), φ = arccos(pf)

Worked example

InputValue
Real power100 kW
Present power factor0.8
Target power factor0.95
  1. tan φ1 = tan(arccos 0.8) = 0.75
  2. tan φ2 = tan(arccos 0.95) = 0.3287
  3. Qc = 100 kW × (0.75 − 0.3287) = 42.132 kVAR

Assumptions

Round up to the next standard capacitor step and check for resonance on harmonic-rich systems.

Inputs and results

InputUnitAllowed or shownNote
Real powerkWgreater than 0 kW
Present power factor(number)greater than 0, up to 1
Target power factor(number)greater than 0, up to 1
ResultUnitAllowed or shownNote
Capacitor ratingkVARShown to 2 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

How the result changes with real power

Real power (kW)Capacitor rating (kVAR)
104.21
2510.53
5021.07
10042.13
20084.26
400168.53
1,000421.32

Other inputs are the same as in the worked example above.

Standards and further reading

Real, apparent and reactive power follow the usual textbook definitions. Tariff and billing rules come from your utility, not from a standard. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter real power, present power factor and target power factor. Change the unit of a value with its selector and the result stays the same.

What does this calculator assume?

Sinusoidal waveforms. Harmonics not considered (check detuning for harmonic-rich loads).

Which calculators should I use next?

Common next steps are kW to kVA and kVAR. The related links at the bottom of this page open them.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 10 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Power and Energy calculatorsAll engineering calculatorsPower Factor Correction in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.