Current THD Calculator

Total harmonic distortion and RMS current from the fundamental and 3rd, 5th and 7th harmonics. With the formula, a worked example and typical values.

Fundamental current 100 A, 3rd harmonic 20 A, 5th harmonic 12 A, 7th harmonic 8 A gives
THD: 24.66% · Total RMS current: 103 A

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

This page calculates THD and total RMS current from fundamental current, 3rd harmonic, 5th harmonic and 7th harmonic. Change any value or its unit and the result updates. The steps below show the working for the default values, so you can check each line against your own method.

Limits of this calculator

Add further harmonic orders from a power-quality analyser for a complete figure.

Cross-check: 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Engineering reference

Engineering reference. Formula and method documented and tested against separately coded reference calculations. Not yet Verified: the evidence listed on this page is still needed.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionIEEE 519; IEC 61000-4-7, IEEE 519-2022; IEC 61000-4-7:2002 + A1:2008 consolidated
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteHarmonic control at the point of common coupling and harmonic measurement instrumentation are relevant. The calculator only combines selected 3rd, 5th and 7th currents; it is not a full spectrum, TDD or compliance assessment.
Cross-check test cases6 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusEngineering reference

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

THD = √(I3² + I5² + I7²) / I1 × 100 Irms = √(I1² + I3² + I5² + I7²)

Worked example

InputValue
Fundamental current100 A
3rd harmonic20 A
5th harmonic12 A
7th harmonic8 A
  1. Harmonic RMS = 24.658 A
  2. THD = 24.658 / 100 × 100 = 24.658 %
  3. Irms = 102.995 A

Assumptions

Add further harmonic orders from a power-quality analyser for a complete figure.

Inputs and results

InputUnitAllowed or shownNote
Fundamental currentAgreater than 0 A
3rd harmonicA0 A or more
5th harmonicA0 A or more
7th harmonicA0 A or more
ResultUnitAllowed or shownNote
THD (%)(number)Shown to 2 decimal places
Total RMS currentAShown to 2 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

How the result changes with fundamental current

Fundamental current (A)THDTotal RMS current (A)
10246.5826.61
2598.6335.11
5049.3255.75
10024.66103
20012.33201.51
4006.16400.76
1,0002.471,000.3

Other inputs are the same as in the worked example above.

Standards and further reading

Check results against your utility's connection requirements and the equipment data sheets. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter fundamental current, 3rd harmonic, 5th harmonic and 7th harmonic. Change the unit of a value with its selector and the result stays the same.

What does this calculator assume?

Only the harmonics entered are included. Magnitudes are RMS.

Which calculators should I use next?

Common next steps are Transformer Efficiency and Losses and Power Factor Correction. The related links at the bottom of this page open them.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Power Systems calculatorsAll engineering calculatorsCurrent THD in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.