Per-Unit Base Conversion Calculator

Convert a per-unit impedance from one MVA and voltage base to another. With the formula, a worked example and typical values.

Impedance on old base (pu) 0.08, old MVA base 10 MVA, old voltage base 11 kV, new MVA base 100 MVA gives
0.8

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

This page calculates impedance on new base from impedance on old base, old MVA base, old voltage base, new MVA base and 1 more input. Change any value or its unit and the result updates. The steps below show the working for the default values, so you can check each line against your own method.

Limits of this calculator

Typical use: put transformer and source impedances on one common system base before adding them.

Cross-check: 10 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Engineering reference

Engineering reference. Formula and method documented and tested against separately coded reference calculations. Not yet Verified: the evidence listed on this page is still needed.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionNot applicable: Textbook power and energy identity (single-phase, three-phase, power factor, per-unit); no governing standard
Standard review stateNot applicable
Scope-screening notenot recorded
Cross-check test cases10 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusEngineering reference

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; exact formula reference; formula source (textbook or standard); next review date.

Formula

Znew = Zold × (Snew / Sold) × (Vold / Vnew)²

Worked example

InputValue
Impedance on old base (pu)0.08
Old MVA base10 MVA
Old voltage base11 kV
New MVA base100 MVA
New voltage base11 kV
  1. Znew = 0.08 × (100 / 10) × (11 / 11)² = 0.8 pu

Assumptions

Typical use: put transformer and source impedances on one common system base before adding them.

Inputs and results

InputUnitAllowed or shownNote
Impedance on old base (pu)(number)greater than 0
Old MVA baseMVAgreater than 0 MVA
Old voltage basekVgreater than 0 kV
New MVA baseMVAgreater than 0 MVA
New voltage basekVgreater than 0 kV
ResultUnitAllowed or shownNote
Impedance on new base (pu)(number)Shown to 5 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

How the result changes with old mva base

Old MVA base (MVA)Impedance on new base
18
2.53.2
51.6
100.8
200.4
400.2
1000.08

Other inputs are the same as in the worked example above.

Standards and further reading

Check results against your utility's connection requirements and the equipment data sheets. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter impedance on old base (pu), old MVA base, old voltage base, new MVA base and new voltage base. Change the unit of a value with its selector and the result stays the same.

What does this calculator assume?

Same physical impedance, different base.

Which calculators should I use next?

Common next steps are Per-Unit Base Values and Fault Level (kA to MVA). The related links at the bottom of this page open them.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 10 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Power Systems calculatorsAll engineering calculatorsPer-Unit Base Conversion in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.