Conductor Resistance vs Temperature Calculator

Resistance of a copper or aluminium conductor at its operating temperature. With the formula, a worked example and typical values.

Resistance at 20 °C 1 Ω, operating temperature (°C) 70, conductor material Copper gives
Resistance at temperature: 1.1965 Ω · Change from 20 °C: 19.65%

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

This page calculates resistance at temperature and change from 20 °C from resistance at 20 °C, operating temperature and conductor material. Change any value or its unit and the result updates. The steps below show the working for the default values, so you can check each line against your own method.

Limits of this calculator

A cable at 90 °C has about 27% more resistance than the cold catalogue value. Voltage drop and loss should use the hot value.

Cross-check: 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Engineering reference

Engineering reference. Formula and method documented and tested against separately coded reference calculations. Not yet Verified: the evidence listed on this page is still needed.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionIEC 60228, 2023 Ed 4.0
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteConductor resistance and construction are in scope. The linear temperature coefficient is a material approximation; confirm actual conductor resistance and temperature limits from the cable standard and manufacturer.
Cross-check test cases6 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusEngineering reference

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

RT = R20 × (1 + α × (T − 20)) α: copper 0.00393, aluminium 0.00403 per °C

Worked example

InputValue
Resistance at 20 °C1 Ω
Operating temperature (°C)70
Conductor materialCopper
  1. Factor = 1 + 0.00393 × (70 − 20) = 1.1965
  2. RT = 1 × 1.1965 = 1.1965 Ω

Assumptions

A cable at 90 °C has about 27% more resistance than the cold catalogue value. Voltage drop and loss should use the hot value.

Inputs and results

InputUnitAllowed or shownNote
Resistance at 20 °CΩgreater than 0 Ω
Operating temperature (°C)(number)-50 or more, up to 250
Conductor material(choice)Copper; Aluminium
ResultUnitAllowed or shownNote
Resistance at temperatureΩShown to 4 decimal places
Change from 20 °C (%)(number)Shown to 2 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

How the result changes with resistance at 20 °c

Resistance at 20 °C (Ω)Resistance at temperature (Ω)Change from 20 °C
0.10.119619.65
0.250.299119.65
0.50.598219.65
11.196519.65
22.39319.65
44.78619.65
1011.96519.65

Other inputs are the same as in the worked example above.

Standards and further reading

Ampacity and grouping factors come from your cable data sheet or your licensed copy of the standard; see STANDARDS.md for the method constants Elecmetric does use. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter resistance at 20 °C, operating temperature (°C) and conductor material. Change the unit of a value with its selector and the result stays the same.

What does this calculator assume?

Linear temperature coefficient. Valid across the normal operating range.

Which calculators should I use next?

Common next steps are Voltage Drop from Conductor Size and Cable Power Loss (I²R). The related links at the bottom of this page open them.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Cable Engineering calculatorsAll engineering calculatorsConductor Resistance vs Temperature in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.