Cable Resistance Calculator

Conductor resistance from length, cross-section and material. With the formula, a worked example and typical values.

Length 100 m, cross-section 16 mm², resistivity at 20 °C (Ω·mm²/m) 0.017241, operating temperature (°C) 20 gives
Resistance: 0.1078 Ω · Per unit length: 1.0776 Ω/km

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

This page calculates resistance and per unit length from length, cross-section and resistivity at 20 °C. Change any value or its unit and the result updates. The steps below show the working for the default values, so you can check each line against your own method.

Limits of this calculator

Use the loop (out and back) value for a two-wire circuit.

Cross-check: 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Engineering reference

Engineering reference. Formula and method documented and tested against separately coded reference calculations. Not yet Verified: the evidence listed on this page is still needed.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionIEC 60228, 2023 Ed 4.0
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteConductor classes, nominal cross-sectional areas and DC resistance are in scope. The calculator uses material resistivity and an approximate temperature correction; verify resistance against the cable datasheet and standard tables.
Cross-check test cases6 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusEngineering reference

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

R = ρ × [1 + α (T − 20)] × L / A

Worked example

InputValue
Length100 m
Cross-section16 mm²
Resistivity at 20 °C (Ω·mm²/m)0.017241
Operating temperature (°C)20
Temperature coefficient (per °C)0.00393
  1. Temperature factor = 1 + α (T − 20) = 1
  2. R = ρ × factor × L / A = 0.10776 Ω

Assumptions

Use the loop (out and back) value for a two-wire circuit.

Inputs and results

InputUnitAllowed or shownNote
Lengthmgreater than 0 m
Cross-sectionmm²greater than 0 mm²
Resistivity at 20 °C (Ω·mm²/m)(number)greater than 0Copper 0.017241, aluminium 0.02826
Operating temperature (°C)(number)-50 or more, up to 250
Temperature coefficient (per °C)(number)greater than 0, up to 0.01Copper 0.00393, aluminium 0.00403
ResultUnitAllowed or shownNote
ResistanceΩShown to 4 decimal places
Per unit lengthΩ/kmShown to 4 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

How the result changes with length

Length (m)Resistance (Ω)Per unit length (Ω/km)
100.01081.0776
250.02691.0776
500.05391.0776
1000.10781.0776
2000.21551.0776
4000.4311.0776
1,0001.07761.0776

Other inputs are the same as in the worked example above.

Standards and further reading

Ampacity and grouping factors come from your cable data sheet or your licensed copy of the standard; see STANDARDS.md for the method constants Elecmetric does use. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter length, cross-section and resistivity at 20 °C (Ω·mm²/m). Change the unit of a value with its selector and the result stays the same.

What does this calculator assume?

Single conductor, one way. Linear temperature correction. DC resistance, no skin or proximity effect.

Which calculators should I use next?

Common next steps are Voltage Drop and Maximum Cable Length. The related links at the bottom of this page open them.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Cable Engineering calculatorsAll engineering calculatorsCable Resistance in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.