AGL Maximum Fittings per Circuit Calculator

Find the largest number of fittings a CCR can supply on an airfield lighting series circuit from CCR rating, lamp power and cable loop.

CCR rating 10 kW, lamp power per fitting 45 W, isolating transformer efficiency 0.85, circuit current 6.6 A gives
Maximum fittings: 140 · Circuit load at that number: 7.948 kW · CCR loading at that number: 79.5% · CCR output voltage: 1,204 V

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

Use this when the regulator is fixed and you need to know how many fittings it can carry. It is the reverse of the CCR loading calculator: it subtracts the cable loss from the usable CCR output and divides by the load of one fitting, including its isolating transformer loss.

Limits of this calculator

Every fitting is assumed to have the same lamp power and transformer efficiency. Confirm the result against the CCR manufacturer output curves, keep spare capacity for future fittings and check the highest brightness step.

Cross-check: 25 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Indicative

Indicative. Estimation only; further engineering checks are required. Basis: Circuit-loading estimate; manufacturer limits govern.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionIEC 61820-1; IEC 61820-1-2; IEC 61820-3-2; FAA AC 150/5345-10H, IEC 61820-1:2019; IEC 61820-1-2:2024; IEC 61820-3-2:2023; FAA AC 150/5345-10H
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteAGL series-circuit and CCR requirements are relevant. The calculator estimates a maximum fitting count from user-entered lamp, transformer and cable data; it does not replace CCR load curves or manufacturer limits.
Cross-check test cases25 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusIndicative

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

Usable = loading × CCR rating Pcable = I² × R × L nmax = ⌊(Usable − Pcable) / (Plamp / ηT)⌋

Worked example

InputValue
CCR rating10 kW
Lamp power per fitting45 W
Isolating transformer efficiency0.85
Circuit current6.6 A
Series cable loop length4,000 m
Series cable resistance3.08 Ω/km
Maximum CCR loading0.8
  1. Usable = 0.8 × 10 kW = 8,000 W
  2. Cable loss = 6.6² × 3.08 Ω/km × 4 km = 536.7 W
  3. Load per fitting = 45 W / 0.85 = 52.94 W
  4. Maximum fittings = ⌊(8,000 − 536.7) / 52.94⌋ = 140

Assumptions

This is the reverse of the CCR sizing calculator. Confirm against the CCR manufacturer's output curves and the isolating transformer open-circuit behaviour, and keep spare capacity for future fittings. Check at the highest brightness step.

Inputs and results

InputUnitAllowed or shownNote
CCR ratingkWgreater than 0 kWRated output of the regulator, from its nameplate
Lamp power per fittingWgreater than 0 WAt the circuit current, from the fitting data sheet
Isolating transformer efficiency(number)greater than 0.5, up to 1From the transformer data sheet at the circuit current
Circuit currentAgreater than 0 A
Series cable loop lengthmgreater than 0 m
Series cable resistanceΩ/kmgreater than 0 Ω/km
Maximum CCR loading(number)0.3 or more, up to 1Fraction of rated kW you are willing to use
ResultUnitAllowed or shownNote
Maximum fittings(number)Shown to 0 decimal places
Circuit load at that numberkWShown to 3 decimal places
Cable lossWShown to 0 decimal places
CCR loading at that number (%)(number)Shown to 1 decimal place
CCR output voltageVShown to 0 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

Typical values

CCR rating (kW)Maximum fittingsCircuit load at that number (kW)CCR loading at that numberCCR output voltage (V)
4503.18479.6482
7.51035.9979.9908
101407.94879.51,204
1521611.97279.81,814
2029215.995802,424
3044323.99803,635

Other inputs are the same as in the worked example above.

Standards and further reading

Photometric and circuit requirements come from the edition of Annex 14 and the regulator's rules that apply at your aerodrome, and from the fitting and regulator manufacturers' data. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter cCR rating, lamp power per fitting, isolating transformer efficiency, circuit current, series cable loop length, series cable resistance and maximum CCR loading. Change the unit of a value with its selector and the result stays the same.

What is the maximum CCR loading setting?

It is the share of the CCR rating you allow to be used, which leaves headroom. Set it to the margin your specification requires.

Why is the number rounded down?

A fraction of a fitting cannot be connected, so the result is the whole number of fittings that fits within the usable output.

How is this different from the CCR loading calculator?

That page starts from the number of fittings and gives the load and the CCR size. This one starts from the CCR and gives the number of fittings.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 25 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Airport and AGL Engineering calculatorsAll engineering calculatorsAGL Maximum Fittings on a CCR in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.