AGL CCR Input Power and Energy Calculator

Estimate CCR input power, apparent and reactive power, annual energy and running cost from output load, efficiency and power factor.

CCR output load 3.713 kW, CCR efficiency 0.9, CCR input power factor 0.9, hours of operation per year 4,380 gives
CCR input power: 4.126 kW · CCR input apparent power: 4.584 kVA · Annual energy: 18,070 kWh · Annual running cost: 144,559

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

Use this to turn a constant current regulator output load into the power it takes from the supply, and into energy and running cost over a year at the hours and tariff you enter.

Limits of this calculator

Efficiency and input power factor are held constant at the load entered. Both fall at light load and low brightness steps, so use the data sheet figures for the step you are costing, cost each step separately and add them. This covers the regulator input only.

Cross-check: 25 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Engineering reference

Engineering reference. Formula and method documented and tested against separately coded reference calculations. Not yet Verified: the evidence listed on this page is still needed.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionIEC 61820-3-2; FAA AC 150/5345-10H, IEC 61820-3-2:2023; FAA AC 150/5345-10H
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteAGL series-circuit power-supply and CCR specification context is relevant. The calculator estimates input power, energy and cost from user-entered efficiency and power factor; it does not model CCR loss curves or metering accuracy.
Cross-check test cases25 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusEngineering reference

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

Pin = Pout / ηCCR S = Pin / pf Q = S × sin(acos pf) E = Pin × hours Cost = E × tariff

Worked example

InputValue
CCR output load3.713 kW
CCR efficiency0.9
CCR input power factor0.9
Hours of operation per year4,380
Energy tariff per kWh8
  1. Input power = 3.713 kW / 0.9 = 4.126 kW
  2. Apparent power = 4.126 / 0.9 = 4.584 kVA, reactive = 1.998 kVAR
  3. Annual energy = 4.126 kW × 4,380 h = 18,070 kWh
  4. Cost = 18,070 kWh × 8 = 144,559

Assumptions

Regulator efficiency and input power factor both fall at light load and low brightness steps, so use the data sheet figure for the step you are costing. This is energy for the regulator input only.

Inputs and results

InputUnitAllowed or shownNote
CCR output loadkWgreater than 0 kWCircuit load from the CCR sizing calculator, at the brightness step you are costing
CCR efficiency(number)greater than 0.5, up to 1From the CCR data sheet at this load and brightness step
CCR input power factor(number)greater than 0, up to 1From the CCR data sheet at this load and brightness step
Hours of operation per year(number)greater than 0, up to 8,760At this brightness step
Energy tariff per kWh(number)0 or moreIn your own currency
ResultUnitAllowed or shownNote
CCR input powerkWShown to 3 decimal places
CCR input apparent powerkVAShown to 3 decimal places
CCR input reactive powerkVARShown to 3 decimal places
Annual energykWhShown to 0 decimal places
Annual running cost(number)Shown to 0 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

Typical values

CCR output load (kW)CCR input power (kW)CCR input apparent power (kVA)Annual energy (kWh)Annual running cost
44.4444.93819,467155,733
7.58.3339.25936,500292,000
1011.11112.34648,667389,333
1516.66718.51973,000584,000
2022.22224.69197,333778,667
3033.33337.037146,0001,168,000

Other inputs are the same as in the worked example above.

Standards and further reading

Photometric and circuit requirements come from the edition of Annex 14 and the regulator's rules that apply at your aerodrome, and from the fitting and regulator manufacturers' data. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter cCR output load, cCR efficiency, cCR input power factor, hours of operation per year and energy tariff per kWh. Change the unit of a value with its selector and the result stays the same.

Why cost each brightness step separately?

Output load, efficiency and power factor differ at each step, and the hours at each step differ. Run the calculation once per step and add the results.

What efficiency should I enter?

Use the regulator data sheet figure at the load and brightness step you are costing, not the full-load figure.

Does the result include the lamps and cables?

The output load you enter is what the regulator supplies, so it already includes them. The result adds only the regulator losses.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 25 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.