AGL CCR Loading Calculator

Estimate the load, loop voltage and smallest standard CCR for an airfield ground lighting series circuit from fittings, lamp power and cable length.

Fittings on the circuit 60, lamp power per fitting 45 W, isolating transformer efficiency 0.85, circuit current 6.6 A gives
Total circuit load: 3.713 kW · CCR output voltage: 563 V · Smallest standard CCR: 7.5 kW · Loading of that CCR: 49.5%

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

Use this for a first estimate of the load on an airfield ground lighting series circuit and the constant current regulator (CCR) size it points to. It adds the lamp load, with the isolating transformer efficiency, to the cable loss in the series loop.

Limits of this calculator

This is a simplified estimating model, not a design tool. Confirm the load model and the CCR rating against the fitting, isolating transformer and CCR manufacturer data and the project requirements, and check the highest brightness step, because lamp failures shift the load.

Cross-check: 39 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Engineering reference

Engineering reference. Formula and method documented and tested against separately coded reference calculations. Not yet Verified: the evidence listed on this page is still needed.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionIEC 61820-1; IEC 61820-1-2; IEC 61820-3-2; FAA AC 150/5345-10H, IEC 61820-1:2019; IEC 61820-1-2:2024; IEC 61820-3-2:2023; FAA AC 150/5345-10H
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteAGL fundamental principles, series-circuit requirements and CCR/power-supply requirements are relevant. The calculator estimates circuit load and CCR size; fitting-specific data, cable resistance, regulator limits and project requirements must be verified.
Cross-check test cases39 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusEngineering reference

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

Pt = n × Plamp / ηT + I² × R × L Vout = Pt / I CCR ≥ Pt / max loading

Worked example

InputValue
Fittings on the circuit60
Lamp power per fitting45 W
Isolating transformer efficiency0.85
Circuit current6.6 A
Series cable loop length4,000 m
Series cable resistance3.08 Ω/km
Maximum CCR loading0.8
  1. Lamp load = 60 × 45 W / 0.85 = 3,176.5 W
  2. Cable loss = 6.6² × 3.08 Ω/km × 4 km = 536.7 W
  3. Total = 3.713 kW, Vout = 3,713 / 6.6 = 563 V
  4. Needed rating = 3.713 / 0.8 = 4.64 kW, so 7.5 kW

Assumptions

Confirm against the CCR manufacturer's output curves, the isolating transformer open-circuit behaviour and the project specification. Lamp failures shift the load, so check at the highest brightness step.

Inputs and results

InputUnitAllowed or shownNote
Fittings on the circuit(number)1 or more, up to 500
Lamp power per fittingWgreater than 0 WAt the circuit current, from the fitting data sheet
Isolating transformer efficiency(number)greater than 0.5, up to 1From the transformer data sheet at the circuit current
Circuit currentAgreater than 0 A
Series cable loop lengthmgreater than 0 m
Series cable resistanceΩ/kmgreater than 0 Ω/km
Maximum CCR loading(number)0.3 or more, up to 1Fraction of rated kW you are willing to use
ResultUnitAllowed or shownNote
Total circuit loadkWShown to 3 decimal places
CCR output voltageVShown to 0 decimal places
Cable lossWShown to 0 decimal places
Smallest standard CCRkWShown to 1 decimal place
Loading of that CCR (%)(number)Shown to 1 decimal place

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

Typical values

Fittings on the circuitTotal circuit load (kW)CCR output voltage (V)Smallest standard CCR (kW)Loading of that CCR
201.595242439.9
402.654402466.4
603.7135637.549.5
804.7727237.563.6
1005.8318837.577.7

Other inputs are the same as in the worked example above.

Standards and further reading

Photometric and circuit requirements come from the edition of Annex 14 and the regulator's rules that apply at your aerodrome, and from the fitting and regulator manufacturers' data. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter fittings on the circuit, lamp power per fitting, isolating transformer efficiency, circuit current, series cable loop length, series cable resistance and maximum CCR loading. Change the unit of a value with its selector and the result stays the same.

Why does the cable loss matter in a series circuit?

The same current flows through every fitting and through the whole cable loop, so the loop resistance dissipates I² × R. The regulator has to supply it on top of the lamp load.

Which CCR sizes does it choose from?

The standard sizes listed in the assumptions below. If your manufacturer offers other ratings, take the required load and select from their range.

Can I rely on this for a project design?

Not on its own. Use it to screen options, then verify with the manufacturer output curves, the isolating transformer open-circuit behaviour and the project specification.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 39 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.