Elecmetric

AGL Load with Failed Lamps Calculator

With the formula, a worked example and typical values.

Fittings on the circuit 60, failed lamps (open circuit) 3, lamp power per fitting 45 W, isolating transformer efficiency 0.85 gives
Circuit load, all lamps working: 3.713 kW · Circuit load with failed lamps: 3.584 kW · Change in load: -129 W

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

This page calculates circuit load, all lamps working, circuit load with failed lamps, change in load and 2 more results from fittings on the circuit, failed lamps, lamp power per fitting, isolating transformer efficiency and 4 more inputs. Change any value or its unit and the result updates. The steps below show the working for the default values, so you can check each line against your own method.

Limits of this calculator

A real open-secondary transformer is not a fixed power. Its voltage and loss depend on the core design, so treat the result as a first estimate and confirm it with the transformer manufacturer. Several failures in a row can still push the CCR toward its overvoltage or open-circuit protection.

Cross-check: 30 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Indicative

Indicative. Estimation only; further engineering checks are required. Basis: Open-secondary transformer treated as a fixed input power; the real value depends on the core design.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionIEC 61820-1-2; FAA AC 150/5345-47B, IEC 61820-1-2:2024; FAA AC 150/5345-47B (30 June 2005)
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteAGL series-circuit and isolation-transformer context is relevant. Open-secondary voltage/power behaviour is manufacturer-specific; the calculator requires user-entered failed-lamp/open-secondary assumptions and is indicative.
Cross-check test cases30 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusIndicative

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

P0 = n × Plamp / ηT + I² R L Pf = (n − f) × Plamp / ηT + f × Popen + I² R L Vout = Pf / I

Worked example

InputValue
Fittings on the circuit60
Failed lamps (open circuit)3
Lamp power per fitting45 W
Isolating transformer efficiency0.85
Transformer input power with the secondary open10 W
Circuit current6.6 A
Series cable loop length4,000 m
Series cable resistance3.08 Ω/km
  1. Fitting load = 45 W / 0.85 = 52.94 W, cable loss = 536.7 W
  2. All working: 60 × 52.94 + 536.7 = 3,713.1 W
  3. 3 failed: 57 × 52.94 + 3 × 10 + 536.7 = 3,584.3 W
  4. Vout = 3,584 / 6.6 = 543 V

Assumptions

A real open-secondary transformer is not a fixed power. Its voltage and loss depend on the core design, so treat the result as a first estimate and confirm it with the transformer manufacturer. Several failures in a row can still push the CCR toward its overvoltage or open-circuit protection.

Inputs and results

InputUnitAllowed or shownNote
Fittings on the circuit(number)1 or more, up to 500
Failed lamps (open circuit)(number)0 or more, up to 500
Lamp power per fittingWgreater than 0 WAt the circuit current, from the fitting data sheet
Isolating transformer efficiency(number)greater than 0.5, up to 1
Transformer input power with the secondary openW0 W or moreExample value only. Use the transformer data sheet or a measurement
Circuit currentAgreater than 0 A
Series cable loop lengthmgreater than 0 m
Series cable resistanceΩ/kmgreater than 0 Ω/km
ResultUnitAllowed or shownNote
Circuit load, all lamps workingkWShown to 3 decimal places
Circuit load with failed lampskWShown to 3 decimal places
Change in loadWShown to 0 decimal places
Change as % of the working load(number)Shown to 1 decimal place
CCR output voltage with failed lampsVShown to 0 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

How the result changes with lamp power per fitting

Lamp power per fitting (W)Circuit load, all lamps working (kW)Circuit load with failed lamps (kW)Change in load (W)
4.50.8540.86814
11.31.3341.324-10
22.52.1252.075-49
453.7133.584-129
906.896.602-288
18013.24312.637-605
45032.30130.743-1,558

Other inputs are the same as in the worked example above.

Standards and further reading

Photometric and circuit requirements come from the edition of Annex 14 and the regulator's rules that apply at your aerodrome, and from the fitting and regulator manufacturers' data. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter fittings on the circuit, failed lamps (open circuit), lamp power per fitting, isolating transformer efficiency, transformer input power with the secondary open, circuit current, series cable loop length and series cable resistance. Change the unit of a value with its selector and the result stays the same.

What does this calculator assume?

Each failed lamp leaves its transformer drawing a fixed open-secondary power. Resistive series circuit, power factor near unity. Current held at the circuit value by the CCR.

Which calculators should I use next?

Common next steps are AGL Series Circuit Load and CCR Size, AGL Isolating Transformer Current and Loading and AGL Lamp Life at a Different Circuit Current. The related links at the bottom of this page open them.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 30 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Airport and AGL Engineering calculatorsAll engineering calculatorsAGL Circuit Load with Failed Lamps in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.