AGL Isolating Transformer Formulas
AGL isolating transformer formulas: the secondary lamp current, the lamp voltage, the primary voltage drop and the loading of a series transformer.
The formulas
| To find | Formula |
|---|---|
| Secondary lamp current | Is = Ip × Isr / Ipr |
| Lamp voltage | Vs = Plamp / Is |
| Input power from the series circuit | Pin = Plamp / ηT |
| Primary voltage drop | Vp = Pin / Ip |
| Transformer loading | Loading = Plamp / Prated |
A series isolating transformer passes the circuit current from its primary to its secondary in the ratio of its rated currents, so a 6.6/6.6 A unit gives the lamp the circuit current and a 6.6/20 A unit gives it about three times the circuit current. Ip is the circuit current at the brightness step, Ipr and Isr the rated primary and secondary currents from the nameplate, Plamp the lamp power at the secondary current, Prated the transformer rating and ηT its efficiency at that current. The current ratio is the ideal one, and the lamp power is taken as a fixed figure, so look it up at the secondary current that the result shows. Primary drop is the voltage the transformer takes from the series loop. An open secondary, such as a failed lamp, is not modelled and needs the manufacturer's data on open-circuit voltage and core saturation. The values are examples.
Worked example: a 6.6/6.6 A transformer with a 45 W lamp, rated 100 W
The circuit current is 6.6 A and the efficiency is 0.85.
- Is = 6.6 × 6.6 / 6.6 = 6.6 A
- Vs = 45 / 6.6 = 6.818 V
- Pin = 45 / 0.85 = 52.94 W
- Vp = 52.94 / 6.6 = 8.021 V
- Loading = 45 / 100 = 45%
Worked example: a 6.6/20 A transformer at 3.4 A with a 30 W lamp, rated 200 W
The efficiency is 0.8.
- Is = 3.4 × 20 / 6.6 = 10.3 A
- Vs = 30 / 10.3 = 2.912 V
- Pin = 30 / 0.8 = 37.5 W, so Vp = 37.5 / 3.4 = 11.03 V
- Loading = 30 / 200 = 15%
Secondary current of a 6.6/20 A transformer at each step of a five-step circuit
| Circuit current | Secondary current |
|---|---|
| 2.8 A | 8.485 A |
| 3.4 A | 10.3 A |
| 4.1 A | 12.42 A |
| 5.2 A | 15.76 A |
| 6.6 A | 20 A |
Frequently asked questions
Why use an isolating transformer?
It separates each lamp from the series cable, so one failed lamp does not break the circuit and the lamp is not at the cable voltage.
Why is the lamp power a fixed number here?
A lamp is not a fixed resistance. Its power changes with the current, so the data sheet figure at the secondary current gives the right answer, not the figure at full current.
What does loading above 100% mean?
The lamp needs more power than the transformer is rated for. Use a larger transformer.
Where do the efficiency figures come from?
From the transformer data sheet at the circuit current. Efficiency is lower at light load, so it changes with the brightness step.
Related
AGL Series Circuit Load and CCR Sizing FormulasAGL Maximum Fittings on a CCR FormulasTransformer FormulasTransformer Efficiency FormulasAirport and AGL calculatorsThree-Phase Power FormulasPower Factor and the Power TriangleAC Circuit Formulas: Reactance and ImpedanceVoltage Drop Formulas for CablesInduction Motor FormulasLighting Formulas: Lux, Lumens and CandelaBattery Formulas: Capacity and RuntimeSolar PV Formulas: Array Size and StringsCapacitor Formulas: Energy and RC Time ConstantEarthing Formulas: Earth Rod and Fault LoopCable Size Formulas: Current and Short-CircuitEnergy and Cost Formulas: kWh and PaybackGenerator Formulas: kVA, Current and FuelUPS Formulas: kVA, DC Current and BatteryHarmonics Formulas: THD and True Power FactorShort-Circuit Formulas: Fault Level by MVAUnbalance Formulas: Voltage and Neutral CurrentResistor Formulas: Series, Parallel, DividerMotor Starting Formulas: DOL, Star-DeltaCircuit Breaker Formulas: Rating and TripCooling Formulas: Airflow and Heat LoadHeating Formulas: Energy and Heater PowerPer-Unit Formulas: Base Values and ImpedanceLED Formulas: Resistor Value and PowerConduit Fill Formulas: Percent Fill and SizeLightning Protection Formulas: Rolling SpherePump Formulas: Hydraulic, Shaft and Motor PowerFan Formulas: Air Power and Affinity LawsInductor Formulas: Energy and L/R Time ConstantRMS, Peak and Average Value FormulasResonance Formulas: Frequency, Q, BandwidthMotor Efficiency Formulas: Input and SavingsDemand, Load and Diversity Factor FormulasCable Tray Fill Formulas: Area and Cable CountConductor Resistance Formulas and TemperatureTransmission Line Formulas: Drop and LossesStar-Delta Conversion Formulas for Resistors4-20 mA Loop Formulas: Scaling and ResistorCable Loss Formulas: Power and Annual CostOp-Amp Formulas: Inverting and Non-Inverting555 Timer Formulas: Frequency and Duty CycleThévenin and Norton FormulasWheatstone Bridge Formulas: Balance and OutputConductor Force Formulas: Short-Circuit ForcesCT Burden Formulas: Lead Resistance and VAGear and Belt Drive Formulas: Speed and TorqueSkin Effect Formulas: Skin DepthRC Filter Formulas: Cutoff Frequency and GainRectifier Ripple Formulas: Capacitor FilterBuck and Boost Converter Formulas: Duty CycleHeat Sink Formulas: Junction TemperatureBattery Pack Formulas: Series and ParallelMotor Acceleration Time FormulasZener Regulator Formulas: Series ResistorBJT Bias Formulas: Voltage Divider BiasPt100 RTD Formulas: Resistance and TemperatureNTC Thermistor Formulas: Beta EquationFusing Current Formulas: Wire Fuse EstimateFlywheel Formulas: Stored EnergyLinear Regulator Formulas: Power and EfficiencyMOSFET Loss Formulas: Conduction and SwitchingRelay Coil Formulas: Current and ResistorTransformer Inrush Current FormulasBattery Charge Time FormulasWind Turbine Power Formulas: Betz LimitDetuning Reactor Formulas: Capacitor BanksTransformer Tap Changer FormulasCable Pulling Tension FormulasInsulation Resistance Formulas: PI and DARPower Transfer and Power Angle FormulasSolar Panel Temperature Derating FormulasVoltage Change and Flicker FormulasSoft Starter and VFD Sizing FormulasEarth Fault Loop and RCD FormulasBattery Internal Resistance FormulasBusbar Size and Short-Circuit FormulasADC Resolution and Sampling FormulasCapacitor Switching Inrush FormulasCable Charging Current FormulasSolar DC to AC Ratio FormulasMeasurement Uncertainty FormulasParallel Transformer Load Sharing FormulasPeukert Law and Battery Runtime FormulasCapacitor Discharge Time FormulasHydraulic Power and Cylinder Force FormulasThermocouple Voltage FormulasTransformer Vector Group FormulasPower Supply Hold-Up Time FormulasHoist and Lift Power FormulasCompressor Power FormulasRectifier Bridge Sizing FormulasPCB Trace Width and Current FormulasHeat Pump COP FormulasSound Level and dB Addition FormulasDuty Cycle and RMS Load FormulasSupercapacitor Energy FormulasStep and Touch Voltage FormulasContactor Sizing FormulasInverter-Fed Motor Cable FormulasPneumatic Cylinder Force and Air UseBusbar Temperature Rise FormulasMotor Temperature Rise FormulasBattery Storage Round-Trip EfficiencyThermal Time Constant FormulasSolar Charge Controller Sizing FormulasPoint Illuminance FormulasGenerator Droop and Load Sharing FormulasTwo-Wattmeter Method FormulasVFD Braking Resistor FormulasLoad Bank Test FormulasTransformer Cooling Class Rating FormulasEnergy Meter Multiplier FormulasOvercurrent Relay Curve FormulasSingle-Tuned Harmonic Filter FormulasCable Sheath Circulating Current FormulasDifferential Protection Slope FormulasEarth Electrode Spacing FormulasSolar Array Row Spacing FormulasDC Lighting Voltage Drop FormulasTransformer Loss of Life FormulasMotor Start Voltage Dip in the Cable FormulasNeutral Earthing Resistor FormulasCable I²t Withstand Check FormulasMotor Locked-Rotor Code Letter FormulasSynchronous Speed and Pole FormulasBattery C-Rate and Cycle Life FormulasEV Charging Time FormulasConveyor Belt Power FormulasParallel Plate Capacitor FormulasSolenoid and Coil Inductance FormulasPower Factor Correction Payback FormulasTransformer Through-Fault Current FormulasTransformer EMF Equation FormulasDelta-Star Resistor Conversion FormulasCurrent Shunt Resistor FormulasSolar Energy Yield and Degradation FormulasElectrolysis and Faraday’s Law FormulasAGL CCR Input Power and Energy FormulasAGL Brightness Step FormulasAGL Lamp Life FormulasComplex Number Formulas: Polar and RectangularPhasor Addition Formulas: Sum and DifferencePercentage Error Formulas for MeasurementsTrigonometry Formulas for Electrical EngineersMean and Standard Deviation FormulasQuadratic, Logarithm and Power FormulasPercentage, Ratio and Rounding FormulasProbability, Combinations and Binomial FormulasConversion Centre