Earth Fault Loop and RCD Formulas
Earth fault loop formulas: the loop impedance from the supply and the cable, the fault current, the maximum impedance for a breaker and the limit with an RCD.
The formulas
| To find | Formula |
|---|---|
| Loop impedance | Zs = Ze + (R1 + R2) |
| Resistance of line and protective conductor | R1 + R2 = ρ × L × (1 / S1 + 1 / S2) |
| Resistance when hot | R(hot) = R(20 °C) × (1 + α × (θ − 20)) |
| Earth fault current | If = U0 / Zs |
| Largest loop impedance for a breaker | Zs(max) = U0 / Ia |
| Largest earth resistance with an RCD | RA ≤ 50 V / IΔn |
Ze is the impedance of the supply side of the loop in ohms, L the cable length in metres, S1 and S2 the line and protective conductor areas in mm², ρ the resistivity in Ω·m (copper 1.7241e-8 at 20 °C), α the temperature coefficient (0.00393 for copper), U0 the voltage from line to earth, Ia the current that makes the device trip in the required time (for a type B breaker, the usual rule is 5 × In) and IΔn the rated residual current of the RCD. The 50 V limit for the touch voltage is the usual value for normal conditions and the trip times and the limit come from the standard you work to, so use your own. The resistance is taken at the working temperature because the loop must trip with hot cables.
Worked example: a 25 m final circuit
Ze = 0.35 Ω, 2.5 mm² line conductor and 1.5 mm² protective conductor, copper, 230 V, protected by a 20 A type B breaker.
- R1 + R2 = 1.7241e-8 × 25 × (1 / 2.5 + 1 / 1.5) × 10⁶ = 0.4598 Ω at 20 °C
- Hot (70 °C): 0.4598 × (1 + 0.00393 × 50) = 0.5501 Ω
- Zs = 0.35 + 0.5501 = 0.9001 Ω
- If = 230 / 0.9001 = 255.5 A
- The breaker needs 5 × 20 = 100 A, so Zs(max) = 230 / 100 = 2.3 Ω, and the circuit passes
Worked example: earth resistance with a 30 mA RCD
- RA ≤ 50 / 0.03 = 1,667 Ω
Largest earth resistance by RCD rating (50 V limit)
| RCD rating | Largest RA |
|---|---|
| 10 mA | 5,000 Ω |
| 30 mA | 1,667 Ω |
| 100 mA | 500 Ω |
| 300 mA | 166.7 Ω |
| 500 mA | 100 Ω |
Frequently asked questions
What is the loop impedance?
The total impedance of the path of a fault current: from the source through the line conductor to the fault and back through the protective conductor and the earth path.
Why calculate with the cable hot?
The resistance of copper rises with temperature, and a fault current flows when the cable is already warm, so the cold value would give a result that is too good.
Does an RCD replace a good earth?
No. An RCD trips on a small leakage and makes a high earth resistance acceptable for shock protection, but the earth is still needed to give the RCD a path and the fault current.
Which supply type is this for?
The loop formulas are for a TN system where the fault current returns through the protective conductor. For a TT system use the earth resistance and the RCD rule instead.
Related
Earthing FormulasCircuit Breaker FormulasConductor Resistance FormulasEarthing calculatorsThree-Phase Power FormulasPower Factor and the Power TriangleAC Circuit Formulas: Reactance and ImpedanceVoltage Drop Formulas for CablesTransformer Formulas: Current and Fault LevelInduction Motor FormulasLighting Formulas: Lux, Lumens and CandelaBattery Formulas: Capacity and RuntimeSolar PV Formulas: Array Size and StringsCapacitor Formulas: Energy and RC Time ConstantCable Size Formulas: Current and Short-CircuitEnergy and Cost Formulas: kWh and PaybackGenerator Formulas: kVA, Current and FuelUPS Formulas: kVA, DC Current and BatteryHarmonics Formulas: THD and True Power FactorShort-Circuit Formulas: Fault Level by MVAUnbalance Formulas: Voltage and Neutral CurrentResistor Formulas: Series, Parallel, DividerMotor Starting Formulas: DOL, Star-DeltaCooling Formulas: Airflow and Heat LoadHeating Formulas: Energy and Heater PowerPer-Unit Formulas: Base Values and ImpedanceLED Formulas: Resistor Value and PowerConduit Fill Formulas: Percent Fill and SizeLightning Protection Formulas: Rolling SphereTransformer Efficiency and Regulation FormulasPump Formulas: Hydraulic, Shaft and Motor PowerFan Formulas: Air Power and Affinity LawsInductor Formulas: Energy and L/R Time ConstantRMS, Peak and Average Value FormulasResonance Formulas: Frequency, Q, BandwidthMotor Efficiency Formulas: Input and SavingsDemand, Load and Diversity Factor FormulasCable Tray Fill Formulas: Area and Cable CountTransmission Line Formulas: Drop and LossesStar-Delta Conversion Formulas for Resistors4-20 mA Loop Formulas: Scaling and ResistorCable Loss Formulas: Power and Annual CostOp-Amp Formulas: Inverting and Non-Inverting555 Timer Formulas: Frequency and Duty CycleThévenin and Norton FormulasWheatstone Bridge Formulas: Balance and OutputConductor Force Formulas: Short-Circuit ForcesCT Burden Formulas: Lead Resistance and VAGear and Belt Drive Formulas: Speed and TorqueSkin Effect Formulas: Skin DepthRC Filter Formulas: Cutoff Frequency and GainRectifier Ripple Formulas: Capacitor FilterBuck and Boost Converter Formulas: Duty CycleHeat Sink Formulas: Junction TemperatureBattery Pack Formulas: Series and ParallelMotor Acceleration Time FormulasZener Regulator Formulas: Series ResistorBJT Bias Formulas: Voltage Divider BiasPt100 RTD Formulas: Resistance and TemperatureNTC Thermistor Formulas: Beta EquationFusing Current Formulas: Wire Fuse EstimateFlywheel Formulas: Stored EnergyLinear Regulator Formulas: Power and EfficiencyMOSFET Loss Formulas: Conduction and SwitchingRelay Coil Formulas: Current and ResistorTransformer Inrush Current FormulasBattery Charge Time FormulasWind Turbine Power Formulas: Betz LimitDetuning Reactor Formulas: Capacitor BanksTransformer Tap Changer FormulasCable Pulling Tension FormulasInsulation Resistance Formulas: PI and DARPower Transfer and Power Angle FormulasSolar Panel Temperature Derating FormulasVoltage Change and Flicker FormulasSoft Starter and VFD Sizing FormulasBattery Internal Resistance FormulasBusbar Size and Short-Circuit FormulasADC Resolution and Sampling FormulasCapacitor Switching Inrush FormulasCable Charging Current FormulasSolar DC to AC Ratio FormulasMeasurement Uncertainty FormulasParallel Transformer Load Sharing FormulasPeukert Law and Battery Runtime FormulasCapacitor Discharge Time FormulasHydraulic Power and Cylinder Force FormulasThermocouple Voltage FormulasTransformer Vector Group FormulasPower Supply Hold-Up Time FormulasHoist and Lift Power FormulasCompressor Power FormulasRectifier Bridge Sizing FormulasPCB Trace Width and Current FormulasHeat Pump COP FormulasSound Level and dB Addition FormulasDuty Cycle and RMS Load FormulasSupercapacitor Energy FormulasStep and Touch Voltage FormulasContactor Sizing FormulasInverter-Fed Motor Cable FormulasPneumatic Cylinder Force and Air UseBusbar Temperature Rise FormulasMotor Temperature Rise FormulasBattery Storage Round-Trip EfficiencyThermal Time Constant FormulasSolar Charge Controller Sizing FormulasPoint Illuminance FormulasGenerator Droop and Load Sharing FormulasTwo-Wattmeter Method FormulasVFD Braking Resistor FormulasLoad Bank Test FormulasTransformer Cooling Class Rating FormulasEnergy Meter Multiplier FormulasOvercurrent Relay Curve FormulasSingle-Tuned Harmonic Filter FormulasCable Sheath Circulating Current FormulasDifferential Protection Slope FormulasEarth Electrode Spacing FormulasSolar Array Row Spacing FormulasDC Lighting Voltage Drop FormulasTransformer Loss of Life FormulasMotor Start Voltage Dip in the Cable FormulasNeutral Earthing Resistor FormulasCable I²t Withstand Check FormulasMotor Locked-Rotor Code Letter FormulasSynchronous Speed and Pole FormulasBattery C-Rate and Cycle Life FormulasEV Charging Time FormulasConveyor Belt Power FormulasParallel Plate Capacitor FormulasSolenoid and Coil Inductance FormulasPower Factor Correction Payback FormulasTransformer Through-Fault Current FormulasTransformer EMF Equation FormulasDelta-Star Resistor Conversion FormulasCurrent Shunt Resistor FormulasSolar Energy Yield and Degradation FormulasElectrolysis and Faraday’s Law FormulasAGL Series Circuit Load and CCR Sizing FormulasAGL Maximum Fittings on a CCR FormulasAGL Isolating Transformer FormulasAGL CCR Input Power and Energy FormulasAGL Brightness Step FormulasAGL Lamp Life FormulasComplex Number Formulas: Polar and RectangularPhasor Addition Formulas: Sum and DifferencePercentage Error Formulas for MeasurementsTrigonometry Formulas for Electrical EngineersMean and Standard Deviation FormulasQuadratic, Logarithm and Power FormulasPercentage, Ratio and Rounding FormulasProbability, Combinations and Binomial FormulasConversion Centre