Three-Phase Voltage Unbalance Calculator

Percentage voltage unbalance from the three line-to-line voltages, as used for motor derating. With the formula, a worked example and typical values.

Line voltage Vab 400 V, line voltage Vbc 410 V, line voltage Vca 395 V gives
Average line voltage: 401.7 V · Voltage unbalance: 2.07%

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

This page calculates average line voltage and voltage unbalance from line voltage Vab, line voltage Vbc and line voltage Vca. Change any value or its unit and the result updates. The steps below show the working for the default values, so you can check each line against your own method.

Limits of this calculator

A small voltage unbalance causes a much larger current unbalance in an induction motor. Fix the cause before relying on derating.

Cross-check: 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Engineering reference

Engineering reference. Formula and method documented and tested against separately coded reference calculations. Not yet Verified: the evidence listed on this page is still needed.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionANSI/NEMA MG 1, 2021, Part 14.36.2
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteThe calculator uses the maximum-deviation-from-average definition published in NEMA MG 1. IEC 60034-26:2026 addresses effects of unbalanced voltages on three-phase cage motors but uses a different analytical context; do not interchange definitions.
Cross-check test cases6 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusEngineering reference

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

Unbalance % = (max deviation from average / average) × 100

Worked example

InputValue
Line voltage Vab400 V
Line voltage Vbc410 V
Line voltage Vca395 V
  1. Average = (400 + 410 + 395) / 3 = 401.67 V
  2. Largest deviation = 8.33 V
  3. Unbalance = 8.33 / 401.67 × 100 = 2.075 %

Assumptions

A small voltage unbalance causes a much larger current unbalance in an induction motor. Fix the cause before relying on derating.

Inputs and results

InputUnitAllowed or shownNote
Line voltage VabVgreater than 0 V
Line voltage VbcVgreater than 0 V
Line voltage VcaVgreater than 0 V
ResultUnitAllowed or shownNote
Average line voltageVShown to 1 decimal place
Voltage unbalance (%)(number)Shown to 2 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

How the result changes with line voltage vab

Line voltage Vab (V)Average line voltage (V)Voltage unbalance
40281.785.8
100301.766.85
20033540.3
400401.72.07
80053549.53
1,600801.799.58
4,0001,601.7149.74

Other inputs are the same as in the worked example above.

Standards and further reading

These are textbook relationships (Ohm's law, series and parallel networks, AC phasors, three-phase quantities). No standard sets the method; standards apply when the result feeds a design, for example cable or protection selection.

Frequently asked questions

What do I need to enter?

Enter line voltage Vab, line voltage Vbc and line voltage Vca. Change the unit of a value with its selector and the result stays the same.

What does this calculator assume?

Line-to-line voltages measured at the motor terminals. NEMA definition; the IEC method uses symmetrical components and gives slightly different values.

Which calculators should I use next?

Common next steps are Motor Full-Load Current and Neutral Current from Unbalanced Load. The related links at the bottom of this page open them.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Electrical Fundamentals calculatorsAll engineering calculatorsThree-Phase Voltage Unbalance in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.