Electrical heater rating to raise a volume of water or similar liquid by a set temperature in a set time. With the formula, a worked example and typical values.

Liquid volume 1,000 L, temperature rise (K) 40, heating time 2 h, heater and tank efficiency 0.9 gives
Heat energy needed: 46.51 kWh · Heater rating: 25.84 kW

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

This page calculates heat energy needed and heater rating from liquid volume, temperature rise, heating time, heater and tank efficiency and 1 more input. Change any value or its unit and the result updates. The steps below show the working for the default values, so you can check each line against your own method.

Limits of this calculator

Add margin for standing losses on long heat-ups, and check the supply current with the three-phase current calculator.

Cross-check: 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Indicative

Indicative. Estimation only; further engineering checks are required. Basis: Heating estimate without losses unless entered.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionNot applicable: The heat-energy equation is a general thermodynamic identity. Heater sizing standards depend on the equipment and application, not this generic equation.
Standard review stateNot applicable
Scope-screening notenot recorded
Cross-check test cases6 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusIndicative

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; exact formula reference; formula source (textbook or standard); next review date.

Formula

Q = m × c × ΔT P = Q / (t × η)

Worked example

InputValue
Liquid volume1,000 L
Temperature rise (K)40
Heating time2 h
Heater and tank efficiency0.9
Specific heat (kJ/kg·K)4.186
  1. Q = 1,000 kg × 4.186 × 40 K = 167.4 MJ = 46.51 kWh
  2. P = 46.51 kWh / (2 h × 0.9) = 25.84 kW

Assumptions

Add margin for standing losses on long heat-ups, and check the supply current with the three-phase current calculator.

Inputs and results

InputUnitAllowed or shownNote
Liquid volumeLgreater than 0 L
Temperature rise (K)(number)greater than 0, up to 100
Heating timehgreater than 0 h
Heater and tank efficiency(number)greater than 0, up to 1
Specific heat (kJ/kg·K)(number)0.5 or more, up to 10
ResultUnitAllowed or shownNote
Heat energy neededkWhShown to 2 decimal places
Heater ratingkWShown to 2 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

How the result changes with liquid volume

Liquid volume (L)Heat energy needed (kWh)Heater rating (kW)
1004.652.58
25011.636.46
50023.2612.92
1,00046.5125.84
2,00093.0251.68
4,000186.04103.36
10,000465.11258.4

Other inputs are the same as in the worked example above.

Standards and further reading

Lamp and luminaire data come from the manufacturer; the illuminance targets that apply come from your project specification and local regulation. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter liquid volume, temperature rise (K), heating time, heater and tank efficiency and specific heat (kJ/kg·K). Change the unit of a value with its selector and the result stays the same.

What does this calculator assume?

1 L of water is 1 kg. Losses during heating are lumped in the efficiency.

Which calculators should I use next?

Common next steps are Current from Power (kW to Amps) and Appliance Running Cost (Energy and Cost). The related links at the bottom of this page open them.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Lighting and Facilities calculatorsAll engineering calculatorsHeater Power for Heating a Liquid in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.