Fan and Pump Affinity Laws Calculator

Flow, head and power at a new speed, showing the energy saved by slowing a fan or pump. With the formula, a worked example and typical values.

Original speed 1,450 rpm, new speed 1,160 rpm, power at original speed 22 kW gives
Flow: 80% · Head or pressure: 64% · Power at new speed: 11.26 kW

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

This page calculates flow, head or pressure, power at new speed and 1 more result from original speed, new speed and power at original speed. Change any value or its unit and the result updates. The steps below show the working for the default values, so you can check each line against your own method.

Limits of this calculator

Static head breaks the cube law, so savings on a pump lifting water are smaller. Below about 50% speed, motor and drive losses matter.

Cross-check: 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Indicative

Indicative. Estimation only; further engineering checks are required. Basis: Idealised affinity laws.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionNot applicable: Fan and pump affinity laws are general similarity relationships. Application limits and performance curves are manufacturer-specific; no single standard governs this generic calculator.
Standard review stateNot applicable
Scope-screening notenot recorded
Cross-check test cases6 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusIndicative

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; exact formula reference; formula source (textbook or standard); next review date.

Formula

Q2/Q1 = N2/N1 H2/H1 = (N2/N1)² P2/P1 = (N2/N1)³

Worked example

InputValue
Original speed1,450 rpm
New speed1,160 rpm
Power at original speed22 kW
  1. Speed ratio = 1,160 / 1,450 = 0.8
  2. Flow = 80 %, head = 64 %
  3. P2 = 22 kW × 0.8³ = 11.26 kW

Assumptions

Static head breaks the cube law, so savings on a pump lifting water are smaller. Below about 50% speed, motor and drive losses matter.

Inputs and results

InputUnitAllowed or shownNote
Original speedrpmgreater than 0 rpm
New speedrpmgreater than 0 rpm
Power at original speedkWgreater than 0 kW
ResultUnitAllowed or shownNote
Flow (% of original)(number)Shown to 1 decimal place
Head or pressure (% of original)(number)Shown to 1 decimal place
Power at new speedkWShown to 2 decimal places
Power saved (%)(number)Shown to 1 decimal place

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

How the result changes with original speed

Original speed (rpm)FlowHead or pressurePower at new speed (kW)
1458006,40011,264
363319.61,021.2717.92
72516025690.11
1,450806411.26
2,90040161.41
5,8002040.18
14,50080.60.01

Other inputs are the same as in the worked example above.

Standards and further reading

Lamp and luminaire data come from the manufacturer; the illuminance targets that apply come from your project specification and local regulation. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter original speed, new speed and power at original speed. Change the unit of a value with its selector and the result stays the same.

What does this calculator assume?

Same fan or pump, same fluid density. System resistance is friction-dominated with little static head. Efficiency stays the same across the speed range.

Which calculators should I use next?

Common next steps are Motor Output Power and Efficiency Loss and Pump Shaft and Motor Power. The related links at the bottom of this page open them.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Lighting and Facilities calculatorsAll engineering calculatorsFan and Pump Affinity Laws in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.