Elecmetric

Fault Current by Fault Type Calculator

Three-phase, line-to-line and line-to-earth fault currents from positive-sequence impedance and the zero-sequence ratio.

System voltage (L-L) 415 V, positive-sequence impedance to the fault 20 mΩ, zero-sequence ÷ positive-sequence impedance 1 gives
Three-phase fault: 11.98 kA · Line-to-line fault: 10.38 kA · Line-to-earth fault: 11.98 kA

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

This page calculates three-phase fault, line-to-line fault and line-to-earth fault from system voltage, positive-sequence impedance to the fault and zero-sequence ÷ positive-sequence impedance. Change any value or its unit and the result updates. The steps below show the working for the default values, so you can check each line against your own method.

Limits of this calculator

The largest value sets the breaking capacity; the smallest earth-fault value must still trip the protective device in time.

Cross-check: 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Indicative

Indicative. Estimation only; further engineering checks are required. Basis: Z2 = Z1, magnitude addition, bolted fault.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionIEC 60909-0, 2026 Ed 3.0
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteShort-circuit calculations for three-phase AC systems, including fault types and sequence networks, are relevant. The calculator is a simplified symmetrical-component estimate and assumes the sequence impedances entered represent the complete source path.
Cross-check test cases6 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusIndicative

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

I3φ = V / (√3 Z1) ILL = (√3 / 2) × I3φ ILE = √3 V / (2 Z1 + Z0)

Worked example

InputValue
System voltage (L-L)415 V
Positive-sequence impedance to the fault20 mΩ
Zero-sequence ÷ positive-sequence impedance1
  1. I3φ = 415 / (√3 × 20 mΩ) = 11.98 kA
  2. ILL = 0.866 × I3φ = 10.375 kA
  3. ILE = √3 × 415 / ((2 + 1) × 20 mΩ) = 11.98 kA

Assumptions

The largest value sets the breaking capacity; the smallest earth-fault value must still trip the protective device in time.

Inputs and results

InputUnitAllowed or shownNote
System voltage (L-L)Vgreater than 0 V
Positive-sequence impedance to the faultmΩgreater than 0 mΩ
Zero-sequence ÷ positive-sequence impedance(number)0.1 or more, up to 20About 1 for a solidly earthed transformer secondary, often 2 to 5 at the end of a cable run
ResultUnitAllowed or shownNote
Three-phase faultkAShown to 2 decimal places
Line-to-line faultkAShown to 2 decimal places
Line-to-earth faultkAShown to 2 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

How the result changes with system voltage (l-l)

System voltage (L-L) (V)Three-phase fault (kA)Line-to-line fault (kA)Line-to-earth fault (kA)
41.51.21.041.2
10432.63
20865.26
41511.9810.3811.98
83023.9620.7523.96
1,66047.9241.547.92
4,150119.8103.75119.8

Other inputs are the same as in the worked example above.

Standards and further reading

This is a first estimate. A protection study and the manufacturer's ratings and time-current curves decide the final selection. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter system voltage (L-L), positive-sequence impedance to the fault and zero-sequence ÷ positive-sequence impedance. Change the unit of a value with its selector and the result stays the same.

What does this calculator assume?

Z2 = Z1. Impedances combined as magnitudes (no angle), slightly conservative. Bolted fault, no arc resistance.

Which calculators should I use next?

Common next steps are Cable Short-Circuit Withstand and Fault Level (kA to MVA). The related links at the bottom of this page open them.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Electrical Protection calculatorsAll engineering calculatorsFault Current by Fault Type in Elecmetric