Transformer Fault Current Calculator

Calculate the prospective three-phase short-circuit current at a transformer secondary from kVA, voltage and impedance percent, with formula and examples.

Transformer rating 1,000 kVA, secondary voltage (L-L) 415 V, impedance 5 gives
27.82 kA

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

Use this for a first estimate of the short-circuit current available at the secondary terminals of a transformer, for example when checking the breaking capacity of the breaker or switchgear that will be connected there.

Limits of this calculator

This is an upper bound. It treats the supply as an infinite source and ignores cable impedance, so the real fault current at a downstream board is lower. It is not a substitute for a short-circuit study, and the equipment rating must still be read from the manufacturer data.

Cross-check: 10 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Indicative

Indicative. Estimation only; further engineering checks are required. Basis: Infinite source, terminal fault, cable impedance ignored (upper bound).

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionIEC 60909-0, 2026 Ed 3.0
Standard review statePublic-scope screened; licensed clause review still pending
Scope-screening noteShort-circuit current calculation for three-phase AC systems. The calculator is a transformer-impedance estimate and does not assemble a complete network model or apply every IEC correction factor.
Cross-check test cases10 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusIndicative

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; licensed clause-by-clause standard review; exact formula reference; formula source (textbook or standard); next review date.

Formula

Isc = S / (√3 × V × Z%/100)

Worked example

InputValue
Transformer rating1,000 kVA
Secondary voltage (L-L)415 V
Impedance5
  1. Full-load current = S / (√3 × V) = 1,391.2 A
  2. Isc = 1,391.2 / 0.05 = 27,824 A

Assumptions

Including source and cable impedance lowers the value. Use as a conservative first check.

Inputs and results

InputUnitAllowed or shownNote
Transformer ratingkVAgreater than 0 kVA
Secondary voltage (L-L)Vgreater than 0 V
Impedance(number)greater than 0, up to 100Percent, from the nameplate
ResultUnitAllowed or shownNote
Fault current at terminalskAShown to 2 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

Typical values

Transformer rating (kVA)Fault current at terminals (kA)
2506.96
50013.91
1,00027.82
1,60044.52
2,00055.65

Other inputs are the same as in the worked example above.

Standards and further reading

This is a first estimate. A protection study and the manufacturer's ratings and time-current curves decide the final selection. These are named as background reading. Elecmetric does not embed clause text or rating tables, and the reviewer record for this calculator is separate from this list.

Frequently asked questions

What do I need to enter?

Enter transformer rating, secondary voltage (L-L) and impedance. Change the unit of a value with its selector and the result stays the same.

Is this the same as a short-circuit current calculator?

It answers the most common version of that question: the three-phase fault level at a transformer secondary. Faults further along a cable run, or with a weak supply, need the source and cable impedance included, which this calculator does not do.

Why is the result called an upper bound?

Adding the utility source impedance and the cable impedance always lowers the fault current. Ignoring them gives the highest value, which is the safe side for a first check of breaker breaking capacity.

What impedance do I enter?

Use the impedance voltage in percent from the transformer nameplate or data sheet. Typical distribution transformers are around 4 to 6 percent, but use the actual figure.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 10 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Electrical Protection calculatorsAll engineering calculatorsTransformer Fault Current in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.