50 kW to Amps

50 kW is 217.4 A at 230 V and 416.7 A at 120 V (single-phase, power factor 1). Table for DC and three-phase, power factor 0.8, and the formula.

Current217.4 A

50 kW at 230 V, single-phase, power factor 1 =
217.4 A

Formula

I = P × 1,000 / V (DC) I = P × 1,000 / (V × pf) (single-phase) I = P × 1,000 / (√3 × V × pf) (three-phase)

Worked example

  1. I = 50 × 1,000 / (230 × 1) = 217.4 A
  2. With a power factor of 0.9: I = 50 × 1,000 / (230 × 0.9) = 241.5 A

On other supplies

SupplyVoltageCurrent at pf 1Current at pf 0.8
DC12 V4,167 Anot used
DC24 V2,083 Anot used
DC48 V1,042 Anot used
Single-phase120 V416.7 A520.8 A
Single-phase230 V217.4 A271.7 A
Single-phase240 V208.3 A260.4 A
Three-phase208 V138.8 A173.5 A
Three-phase400 V72.17 A90.21 A
Three-phase415 V69.56 A86.95 A
Three-phase480 V60.14 A75.18 A

Three-phase rows use the line-to-line voltage. DC ignores the power factor.

What 50 kW looks like

50 kW is a fast DC electric vehicle charger, or the load of a small shop or workshop.

This is an estimate of the load current only. Choosing a cable or a breaker also needs the installation method, the ambient temperature, the voltage drop and the rules you work to.

Frequently asked questions

How many amps is 50 kilowatts?

50 kW is 217.4 A on a 230 V single-phase supply and 416.7 A on 120 V, both with a power factor of 1. The current depends on the voltage, so it is a different answer on every supply.

What if the power factor is not 1?

The current rises. At 230 V and a power factor of 0.9, 50 kW draws 241.5 A. Heaters and filament lamps are close to 1, while motors and many power supplies are lower.

What about a three-phase supply?

50 kW on 400 V three-phase at a power factor of 0.8 is 90.21 A. The line voltage is used with the factor √3 (about 1.732).

Related

kW to Amps CalculatorkVA to Amps20 kW to A1 kW to A2 kW to APower ConverterConversion Centre