Elecmetric

2 kW to Amps

2 kW is 8.696 A at 230 V and 16.67 A at 120 V (single-phase, power factor 1). Table for DC and three-phase, power factor 0.8, and the formula.

Current8.696 A

2 kW at 230 V, single-phase, power factor 1 =
8.696 A

Formula

I = P × 1,000 / V (DC) I = P × 1,000 / (V × pf) (single-phase) I = P × 1,000 / (√3 × V × pf) (three-phase)

Worked example

  1. I = 2 × 1,000 / (230 × 1) = 8.696 A
  2. With a power factor of 0.9: I = 2 × 1,000 / (230 × 0.9) = 9.662 A

On other supplies

SupplyVoltageCurrent at pf 1Current at pf 0.8
DC12 V166.7 Anot used
DC24 V83.33 Anot used
DC48 V41.67 Anot used
Single-phase120 V16.67 A20.83 A
Single-phase230 V8.696 A10.87 A
Single-phase240 V8.333 A10.42 A
Three-phase208 V5.551 A6.939 A
Three-phase400 V2.887 A3.608 A
Three-phase415 V2.782 A3.478 A
Three-phase480 V2.406 A3.007 A

Three-phase rows use the line-to-line voltage. DC ignores the power factor.

What 2 kW looks like

2 kW is about the load of an electric kettle or a large hair dryer.

This is an estimate of the load current only. Choosing a cable or a breaker also needs the installation method, the ambient temperature, the voltage drop and the rules you work to.

Frequently asked questions

How many amps is 2 kilowatts?

2 kW is 8.696 A on a 230 V single-phase supply and 16.67 A on 120 V, both with a power factor of 1. The current depends on the voltage, so it is a different answer on every supply.

What if the power factor is not 1?

The current rises. At 230 V and a power factor of 0.9, 2 kW draws 9.662 A. Heaters and filament lamps are close to 1, while motors and many power supplies are lower.

What about a three-phase supply?

2 kW on 400 V three-phase at a power factor of 0.8 is 3.608 A. The line voltage is used with the factor √3 (about 1.732).

Related

kW to Amps CalculatorkVA to Amps1 kW to A3 kW to A5 kW to APower ConverterConversion Centre