3 kW to Amps

3 kW is 13.04 A at 230 V and 25 A at 120 V (single-phase, power factor 1). Table for DC and three-phase, power factor 0.8, and the formula.

Current13.04 A

3 kW at 230 V, single-phase, power factor 1 =
13.04 A

Formula

I = P × 1,000 / V (DC) I = P × 1,000 / (V × pf) (single-phase) I = P × 1,000 / (√3 × V × pf) (three-phase)

Worked example

  1. I = 3 × 1,000 / (230 × 1) = 13.04 A
  2. With a power factor of 0.9: I = 3 × 1,000 / (230 × 0.9) = 14.49 A

On other supplies

SupplyVoltageCurrent at pf 1Current at pf 0.8
DC12 V250 Anot used
DC24 V125 Anot used
DC48 V62.5 Anot used
Single-phase120 V25 A31.25 A
Single-phase230 V13.04 A16.3 A
Single-phase240 V12.5 A15.63 A
Three-phase208 V8.327 A10.41 A
Three-phase400 V4.33 A5.413 A
Three-phase415 V4.174 A5.217 A
Three-phase480 V3.608 A4.511 A

Three-phase rows use the line-to-line voltage. DC ignores the power factor.

What 3 kW looks like

3 kW is about the element of a domestic water heater, or a small portable generator at full output.

This is an estimate of the load current only. Choosing a cable or a breaker also needs the installation method, the ambient temperature, the voltage drop and the rules you work to.

Frequently asked questions

How many amps is 3 kilowatts?

3 kW is 13.04 A on a 230 V single-phase supply and 25 A on 120 V, both with a power factor of 1. The current depends on the voltage, so it is a different answer on every supply.

What if the power factor is not 1?

The current rises. At 230 V and a power factor of 0.9, 3 kW draws 14.49 A. Heaters and filament lamps are close to 1, while motors and many power supplies are lower.

What about a three-phase supply?

3 kW on 400 V three-phase at a power factor of 0.8 is 5.413 A. The line voltage is used with the factor √3 (about 1.732).