Elecmetric

LC Resonance and Q Factor Calculator

Resonant frequency, reactance at resonance and Q of a series RLC circuit. With the formula, a worked example and typical values.

Inductance 10 mH, capacitance 10 µF, series resistance 5 Ω gives
Resonant frequency: 503.29 Hz · Reactance at resonance: 31.623 Ω · Quality factor Q: 6.325

Estimate only. Not engineering or safety advice. Check the result against the applicable standard and the equipment data, and have a competent engineer review it before it is relied on. Terms of use.

Open in the calculator with these values

About this calculator

This page calculates resonant frequency, reactance at resonance, quality factor Q and 1 more result from inductance, capacitance and series resistance. Change any value or its unit and the result updates. The steps below show the working for the default values, so you can check each line against your own method.

Limits of this calculator

Resonance with capacitor banks and system inductance is a real harmonic-amplification risk on industrial networks.

Cross-check: 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review.

Verification status: Engineering reference

Engineering reference. Formula and method documented and tested against separately coded reference calculations. Not yet Verified: the evidence listed on this page is still needed.

What this calculator checks

What remains unverified

Verification register entry

Calculation authorRahul Sharma (author)
Technical reviewNo independent technical review has been carried out
Individual professional approvalNot recorded
Formula referencenot recorded
Standard and editionNot applicable: Textbook circuit identity (Ohm's law, power, series/parallel, AC circuit theory); no governing standard
Standard review stateNot applicable
Scope-screening notenot recorded
Cross-check test cases6 reference vectors (tests/reference_vectors.json)
Review datenot recorded
Next review datenot recorded
StatusEngineering reference

Needed before this calculator can be marked Verified: reviewer name, qualification and review date; exact formula reference; formula source (textbook or standard); next review date.

Formula

f0 = 1 / (2π √(LC)) X0 = √(L / C) Q = X0 / R BW = f0 / Q

Worked example

InputValue
Inductance10 mH
Capacitance10 µF
Series resistance5 Ω
  1. f0 = 1 / (2π √(10 mH × 10 µF)) = 503.292 Hz
  2. X0 = √(L / C) = 31.6228 Ω
  3. Q = 31.623 / 5 = 6.325

Assumptions

Resonance with capacitor banks and system inductance is a real harmonic-amplification risk on industrial networks.

Inputs and results

InputUnitAllowed or shownNote
InductancemHgreater than 0 mH
CapacitanceµFgreater than 0 µF
Series resistanceΩgreater than 0 Ω
ResultUnitAllowed or shownNote
Resonant frequencyHzShown to 2 decimal places
Reactance at resonanceΩShown to 3 decimal places
Quality factor Q(number)Shown to 3 decimal places
BandwidthHzShown to 2 decimal places

How it is calculated

Each input is converted to the base unit of its quantity, the formula above is applied in the order shown in the worked example, and each result is shown in the unit you choose. Results are held at full precision and rounded only for display, except where a step selects a standard size, as the worked example shows. A value outside its allowed range is refused with a message instead of giving a result.

How the result changes with inductance

Inductance (mH)Resonant frequency (Hz)Reactance at resonance (Ω)Quality factor Q
11,591.55102
2.51,006.5815.8113.162
5711.7622.3614.472
10503.2931.6236.325
20355.8844.7218.944
40251.6563.24612.649
100159.1510020

Other inputs are the same as in the worked example above.

Standards and further reading

These are textbook relationships (Ohm's law, series and parallel networks, AC phasors, three-phase quantities). No standard sets the method; standards apply when the result feeds a design, for example cable or protection selection.

Frequently asked questions

What do I need to enter?

Enter inductance, capacitance and series resistance. Change the unit of a value with its selector and the result stays the same.

What does this calculator assume?

Ideal series circuit. Component losses are lumped in R.

Which calculators should I use next?

Common next steps are Inductive and Capacitive Reactance and Series RLC Impedance. The related links at the bottom of this page open them.

How accurate are the results?

Every figure comes from the same tested engine as the Elecmetric calculators and is meant for estimating. 6 reference cases, calculated from textbook formulas coded separately from the engine by the same author, agree with this calculator. This is not an independent review. Check design values against the standard and the equipment data you work to.

Formula guides and reference

Longer explanations with worked examples and tables, written for the same topic.

More Electrical Fundamentals calculatorsAll engineering calculatorsLC Resonance and Q Factor in Elecmetric

Tell us how to improve this page

This opens your email app. Nothing is sent until you press send.