Elecmetric

250 kVA to Amps

250 kVA is 360.8 A at 400 V and 13.12 A at 11 kV (three-phase), and 1,087 A at 230 V single-phase. Table for common supplies and the formula.

Current360.8 A

250 kVA at 400 V, three-phase =
360.8 A

Formula

I = S × 1,000 / V (single-phase) I = S × 1,000 / (√3 × V) (three-phase)

Worked example

  1. Three-phase, 400 V: I = 250 × 1,000 / (√3 × 400) = 360.8 A
  2. Single-phase, 230 V: I = 250 × 1,000 / 230 = 1,087 A

On other supplies

SupplyVoltageCurrent
Single-phase120 V2,083 A
Single-phase230 V1,087 A
Single-phase240 V1,042 A
Three-phase208 V693.9 A
Three-phase400 V360.8 A
Three-phase415 V347.8 A
Three-phase480 V300.7 A
Three-phase690 V209.2 A
Three-phase6,600 V21.87 A
Three-phase11,000 V13.12 A
Three-phase33,000 V4.374 A

Three-phase rows use the line-to-line voltage.

What 250 kVA looks like

250 kVA is a common size for a transformer feeding a small factory or a large building.

This is the rated current only. Cable, breaker and protection settings also depend on the installation, inrush, the rules you work to and the transformer data sheet.

Frequently asked questions

How many amps is 250 kVA?

250 kVA is 360.8 A on a 400 V three-phase supply, 347.8 A at 415 V and 13.12 A at 11 kV. On a 230 V single-phase supply it is 1,087 A. The current depends on the voltage, so there is no single answer.

Why is no power factor needed?

kVA is apparent power, which is voltage times current (times √3 for three-phase). The power factor only matters when you convert kVA to kW.

Is this the rated current of a transformer?

It is the rated line current at that voltage for a balanced load: kVA × 1,000 / (√3 × V). Inrush, overload and fault current are separate questions.

Related

kVA to Amps CalculatorkVA to kW160 kVA to A400 kVA to A630 kVA to ATransformer Sizing CalculatorPower ConverterConversion Centre